KVV

KVV is a China (GB / JB/T / MT cable model codes) cable designation: K = Control Cable; V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of KVV 4x1.5 450/750 V:

  • KVV: K = Control Cable; V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC)
  • 4x1.5 450/750 V: 4 cores, each copper 1.5 mm²; rated voltage 0.45/0.75 kV

Related cable types: KVVR · ZC-KVV · ZC-KVVP · WDZC-KVVR

China (GB / JB/T / MT cable model codes)

SymbolMeaning
KControl Cable
VPolyvinyl Chloride (PVC)
VPolyvinyl Chloride (PVC)

How to read a China (GB / JB/T / MT cable model codes) cable code

How to read a China (GB / JB/T / MT cable model codes) cable code

A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.

What does K mean in a China (GB / JB/T / MT cable model codes) cable code? K means Control Cable.

What does V mean in a China (GB / JB/T / MT cable model codes) cable code? V means Polyvinyl Chloride (PVC).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

KVV as the cable designer builds it, 4x1.5 450/750 V

Overall diameter 9.1 mm, about 130 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.702.8
FillerPP6.7
SheathPVC1.29.1

KVV on a drum

The smallest drum that passes every check, for 9.1 mm and about 130 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1472 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG15 of 17161–165 kg

Barrel at least 15 × OD = 137 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: KVV

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with KVV

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More China (GB / JB/T / MT cable model codes) designations

KVV