KVV
KVV is a China (GB / JB/T / MT cable model codes) cable designation: K = Control Cable; V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of KVV 4x1.5 450/750 V:
KVV: K = Control Cable; V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC)4x1.5 450/750 V: 4 cores, each copper 1.5 mm²; rated voltage 0.45/0.75 kV
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
K | Control Cable |
V | Polyvinyl Chloride (PVC) |
V | Polyvinyl Chloride (PVC) |
How to read a China (GB / JB/T / MT cable model codes) cable code
How to read a China (GB / JB/T / MT cable model codes) cable code
A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.
What does K mean in a China (GB / JB/T / MT cable model codes) cable code? K means Control Cable.
What does V mean in a China (GB / JB/T / MT cable model codes) cable code? V means Polyvinyl Chloride (PVC).
Fire behaviour (EU CPR)
PVC sheath (V).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
KVV as the cable designer builds it, 4x1.5 450/750 V
Overall diameter 9.1 mm, about 130 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.70 | 2.8 |
| Filler | PP | 6.7 | |
| Sheath | PVC | 1.2 | 9.1 |
KVV on a drum
The smallest drum that passes every check, for 9.1 mm and about 130 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 12 of 14 | 72 kg |
| 1,000 m | KTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG | 15 of 17 | 161–165 kg |
Barrel at least 15 × OD = 137 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: KVV