KVVR
KVVR is a China (GB / JB/T / MT cable model codes) cable designation: K = Control Cable; V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC); R = Flexible Cable.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of KVVR 4x1.5 450/750 V:
KVVR: K = Control Cable; V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC); R = Flexible Cable4x1.5 450/750 V: 4 cores, each copper 1.5 mm²; rated voltage 0.45/0.75 kV
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
K | Control Cable |
V | Polyvinyl Chloride (PVC) |
V | Polyvinyl Chloride (PVC) |
R | Flexible Cable |
How to read a China (GB / JB/T / MT cable model codes) cable code
Norwegian type designation (NEK 606 offshore and Norwegian land cables)
| Symbol | Meaning |
|---|---|
K | Paper |
V | Screen (Draka key: aluminium screen; Nexans key: screen, optionally with PVC) |
V | Double Wire Armour (Two Layers) |
R | Ethylene Propylene Rubber (EPR) |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
How to read a China (GB / JB/T / MT cable model codes) cable code
A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.
What does K mean in a China (GB / JB/T / MT cable model codes) cable code? K means Control Cable.
What does V mean in a China (GB / JB/T / MT cable model codes) cable code? V means Polyvinyl Chloride (PVC).
What does R mean in a China (GB / JB/T / MT cable model codes) cable code? R means Flexible Cable.
Fire behaviour (EU CPR)
PVC sheath (V).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
KVVR: equivalents in other countries
Shown for 4x1.5 450/750 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| India | IS 694 | FR FLEXIBLE 4x1,5 1100 V | Close | rated higher: 1100 V (this cable 450/750 V); Insulation 0.7 → 0.6 mm; Sheath 1.2 → 1 mm; Overall diameter 9.51 → 8.63 mm |
No equivalent in: EN 50525-2-11 (rated lower: 300/500 V (this cable 450/750 V)); EN 50525-2-51 (rated lower: 300/500 V (this cable 450/750 V)); DIN VDE 0250-405 (rated lower: 300/500 V (this cable 450/750 V)).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
KVVR as the cable designer builds it, 4x1.5 450/750 V
Overall diameter 9.5 mm, about 140 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.70 | 2.9 |
| Filler | PP | 7.1 | |
| Sheath | PVC | 1.2 | 9.5 |
KVVR on a drum
The smallest drum that passes every check, for 9.5 mm and about 140 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 12 of 14 | 77 kg |
| 1,000 m | KTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG | 16 of 17 | 171–175 kg |
Barrel at least 12 × OD = 114 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: KVVR
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with KVVR
Who makes or stocks this cable?