FR is a BIS type names (India) cable designation: FR = Flame Retardant; PVC = PVC insulation; FR WIRE = FR house wire: one copper conductor, flame-retardant PVC insulation. 1100 V AC (Polycab ETIRA FR). IS 694:2010 (cable code cl. 13); flammability IEC 60332-1 (Polycab).

6 coding systems recognise this code

BIS type names (India)

SymbolMeaning
FRFlame Retardant
PVCPVC insulation
FR WIREFR house wire: one copper conductor, flame-retardant PVC insulation. 1100 V AC (Polycab ETIRA FR). IS 694:2010 (cable code cl. 13); flammability IEC 60332-1 (Polycab)

NEC Article 402 (US fixture wires, NFPA 70)

SymbolMeaning
FFixture Wire, Solid Or 7-Strand
RHeat-Resistant Rubber Or Cross-Linked Synthetic Polymer (Thermoset)

How to read a NEC Article 402 (US fixture wires, NFPA 70) cable code

CEI-UNEL 35011 (Italy)

SymbolMeaning
FFine-Wired In Flexible Cables-Class 5
RPVC Compound (TI1/TI2 Quality, 70 °C)

How to read a CEI-UNEL 35011 (Italy) cable code

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
FPE Or PP + Filling Compound
REthylene Propylene Rubber (EPR)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

BS 6883 / BS 7917 marine cables and BS 7655 compound types

SymbolMeaning
FRFire Resisting (Prysmian BS 6883 / BS 7917 letter: mica glass tape under the insulation); Flame Retardant (BS 7655-1.5 compound types FR 1, FR 2)

How to read a BS 6883 / BS 7917 marine cables and BS 7655 compound types cable code

VG 95218 (German Navy cables)

SymbolMeaning
FRFire Resistant (For Duration Stated Next To This Symbol If Present)

How to read a VG 95218 (German Navy cables) cable code

Fire behaviour (EU CPR)

  • Flame retardant (FR, FR WIRE). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

  • PVC sheath (FR WIRE).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

FR as the cable designer builds it, 1x1.5 1100 V

Overall diameter 2.7 mm, about 20 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.602.7

FR on a drum

The smallest drum that passes every check, for 2.7 mm and about 20 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 3 (390 mm flange), plastic KTG drums (Europe), KTG8 of 2812 kg
1,000 mKTG 3 (390 mm flange), plastic KTG drums (Europe), KTG14 of 2822 kg

Barrel at least 12 × OD = 33 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: FR

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro