TFR-8

TFR-8 is a KS / KEPCO type names (Korea) cable designation: TFR-8 = TFR-8: fire-resistant cable for fire-service circuits: fire-proof layer, XLPE insulation, heat-resistant reinforced layer, flame-retardant PVC sheath; TFR-8 = TFR-8: 0.6/1 kV fire-resistant cable for fire-service circuits, flame-retardant PVC sheath. 0.6/1 kV (Taihan p.50). KS C IEC 60502-1, Taihan standard.

1 coding system recognises this code

KS / KEPCO type names (Korea)

SymbolMeaning
TFR-8TFR-8: fire-resistant cable for fire-service circuits: fire-proof layer, XLPE insulation, heat-resistant reinforced layer, flame-retardant PVC sheath
TFR-8TFR-8: 0.6/1 kV fire-resistant cable for fire-service circuits, flame-retardant PVC sheath. 0.6/1 kV (Taihan p.50). KS C IEC 60502-1, Taihan standard

Fire behaviour (EU CPR)

  • Fire resistant (TFR-8): the circuit keeps working in a fire. That is circuit integrity, classified apart from reaction to fire (EN 13501-3: P and PH classes, 15 to 120 min). It gives no reaction-to-fire class; that one is declared on its own.

  • Flame retardant (TFR-8). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

  • PVC sheath (TFR-8).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Not equivalent, because

IEC 60331 ≠ BS 6387 (C, W, Z) ≠ BS 8491 ≠ EN 50200 (PH) ≠ DIN 4102-12 (E30, E60, E90) ≠ UL 2196

Not equivalent, because Flame or furnace, temperature, mechanical shock, water and what is tested (a cable alone, or a cable with its supports) all differ: a time or class from one test says nothing about another.

IEC 60331

  • Parts 1 and 2: a flame of at least 830 °C with mechanical shock; part 1 for cables over 20 mm, part 2 up to 20 mm; up to 0.6/1 kV. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)
  • Parts 11 and 21: fire alone, at least 750 °C. Sources: IEC 60331-11:1999+A1:2009 (edition 1.1), 5.2 p. 7, Annex A p. 13; IEC 60331-21:1999, cl. 7 and 8, pp. 13 to 15 (read in the standard)
  • Pass: the circuit keeps working for the stated time. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)

BS 6387 (C, W, Z)

  • C: 950 °C for 3 h. W: 650 °C for 15 min, then 15 min with water. Z: 950 °C with a shock every 30 s for 15 min. CWZ: all three passed. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (owner copy) (read in the standard)
  • Cables up to 600/1000 V and 20 mm diameter. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (owner copy) (read in the standard)

BS 8491

EN 50200 (PH)

  • 830 °C with a shock every 5 min, cables up to 20 mm; Annex E adds a water spray. Sources: Prysmian UK, "What's changed since the CWZ test?" (maker's catalogue)
  • Classes PH15, PH30, PH60, PH90, PH120 (EN 13501-3). Sources: EN 13501-3:2005+A1:2009 with draft A2 (cover September 2013), cl 4.3 p. 7; cl 6.3 p. 9; cl 7.2.4.4, 7.2.5.4 pp. 16-17; cl 7.2.6.2 p. 18 (read in a draft)

DIN 4102-12 (E30, E60, E90)

  • The cable with its supports in a furnace on the standard temperature curve, at up to 400 V; E30, E60 and E90 hold only for the support system tested. Sources: Datwyler (N)HXCH FE180 E90 datasheet (maker's catalogue)

UL 2196

  • A furnace on the ASTM E119 time-temperature curve (NFPA 262 Annex A names it for UL 2196). Sources: NFPA 262:2023 (NFPA free access), Annex A, A.1.1.1 (read in the standard)
  • Ratings up to 2 h, with a hose stream after the fire. Sources: research: equivalents map F5 (UL 2196 not read) (typical practice)