RG7H1R
RG7H1R is a CEI-UNEL type names (Italy) cable designation: R = Conductor form: rigid round stranded, copper because there is no A ('Conduttore a corda rigida rotonda'); datasheet class 2 compact; G7 = Insulation: high-modulus ethylene-propylene rubber, HEPR ('gomma etilenpropilenica ad alto modulo'); H1 = Screen: copper tapes or wires ('Schermo a nastri o piattine o fili di rame'); R = Sheath: PVC, quality Rz ('Guaina a base di PVC, qualità TM1, TM2, RZ'); RG7H1R = RG7H1R: single-core medium-voltage cable, copper compact conductor, HEPR (G7) insulation, copper wire and tape screen, PVC sheath. 1,8/3 kV to 26/45 kV (Comcavi); 90 C max operating. IEC 60502 / CEI 20-13 (Comcavi); designation per CEI-UNEL 35011.
1 coding system recognises this code
CEI-UNEL type names (Italy)
| Symbol | Meaning |
|---|---|
R | Conductor form: rigid round stranded, copper because there is no A ('Conduttore a corda rigida rotonda'); datasheet class 2 compact |
G7 | Insulation: high-modulus ethylene-propylene rubber, HEPR ('gomma etilenpropilenica ad alto modulo') |
H1 | Screen: copper tapes or wires ('Schermo a nastri o piattine o fili di rame') |
R | Sheath: PVC, quality Rz ('Guaina a base di PVC, qualità TM1, TM2, RZ') |
RG7H1R | RG7H1R: single-core medium-voltage cable, copper compact conductor, HEPR (G7) insulation, copper wire and tape screen, PVC sheath. 1,8/3 kV to 26/45 kV (Comcavi); 90 C max operating. IEC 60502 / CEI 20-13 (Comcavi); designation per CEI-UNEL 35011 |
Fire behaviour (EU CPR)
PVC sheath (R).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.