ARG7H1R

ARG7H1R is a CEI-UNEL type names (Italy) cable designation: A = Conductor metal: aluminium ('Conduttore in alluminio'); no A would mean copper; R = Conductor form: rigid round stranded, normal or compact ('Conduttore a corda rigida rotonda, costruzione normale o compatta'); datasheet class 2 compact; G7 = Insulation: high-modulus ethylene-propylene rubber, HEPR, 90 C ('gomma etilenpropilenica ad alto modulo'); NOT PVC; H1 = Screen: copper tapes, strips or wires ('Schermo a nastri o piattine o fili di rame'); datasheet: copper wires with counter-spiral copper tape; R = Sheath: PVC, quality TM1/TM2/RZ ('Guaina a base di PVC, qualità TM1, TM2, RZ'); datasheet Rz, red; ARG7H1R = ARG7H1R: single-core medium-voltage cable, aluminium compact conductor, HEPR (G7) insulation, copper wire and tape screen, PVC sheath. 1,8/3 kV to 18/30 kV (Comcavi); 12/20 kV = Uo/U 12/20 kV, Um 24 kV; 90 C max operating, 250 C short circuit. CEI 20-13 and IEC 60502 (Comcavi); CEI 20-13, IEC 60502-2 (La Triveneta); CEI 11-17 for laying; designation per CEI-UNEL 35011.

1 coding system recognises this code

CEI-UNEL type names (Italy)

SymbolMeaning
AConductor metal: aluminium ('Conduttore in alluminio'); no A would mean copper
RConductor form: rigid round stranded, normal or compact ('Conduttore a corda rigida rotonda, costruzione normale o compatta'); datasheet class 2 compact
G7Insulation: high-modulus ethylene-propylene rubber, HEPR, 90 C ('gomma etilenpropilenica ad alto modulo'); NOT PVC
H1Screen: copper tapes, strips or wires ('Schermo a nastri o piattine o fili di rame'); datasheet: copper wires with counter-spiral copper tape
RSheath: PVC, quality TM1/TM2/RZ ('Guaina a base di PVC, qualità TM1, TM2, RZ'); datasheet Rz, red
ARG7H1RARG7H1R: single-core medium-voltage cable, aluminium compact conductor, HEPR (G7) insulation, copper wire and tape screen, PVC sheath. 1,8/3 kV to 18/30 kV (Comcavi); 12/20 kV = Uo/U 12/20 kV, Um 24 kV; 90 C max operating, 250 C short circuit. CEI 20-13 and IEC 60502 (Comcavi); CEI 20-13, IEC 60502-2 (La Triveneta); CEI 11-17 for laying; designation per CEI-UNEL 35011

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Related cables