NYY-G
NYY-G is a TIS 11 type names (Thailand) cable designation: NYY-G = NYY-G: Thai NYY (PVC insulation, PVC inner and outer sheath) with a green-and-yellow protective earth core; NYY-G = NYY-G (Thailand): PVC-insulated copper cores, PVC inner and outer sheath, with a green-and-yellow earth core. 300/500 V (60227 IEC 10) or 450/750 V (Part 101), 70 C (Thai Cable Wires). TIS 11 Part 4-2553 (60227 IEC 10, to 35 mm2, 300/500 V) and TIS 11 Part 101-2553 (NYY-G, 450/750 V).
3 coding systems recognise this code
TIS 11 type names (Thailand)
| Symbol | Meaning |
|---|---|
NYY-G | NYY-G: Thai NYY (PVC insulation, PVC inner and outer sheath) with a green-and-yellow protective earth core |
NYY-G | NYY-G (Thailand): PVC-insulated copper cores, PVC inner and outer sheath, with a green-and-yellow earth core. 300/500 V (60227 IEC 10) or 450/750 V (Part 101), 70 C (Thai Cable Wires). TIS 11 Part 4-2553 (60227 IEC 10, to 35 mm2, 300/500 V) and TIS 11 Part 101-2553 (NYY-G, 450/750 V) |
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
Y | Polyvinyl Chloride (PVC) |
Y | Polyvinyl Chloride (PVC) |
G | Helical Galvanized Steel Tape |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
DIN VDE 0250 cords, control and special cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
Y | Polyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General |
Y | Polyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General |
G | Rubber / Elastomer Insulation Or Sheath (Older Editions: Natural Rubber NR Or SBR) |
How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code
Fire behaviour (EU CPR)
PVC sheath (NYY-G).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NYY-G as the cable designer builds it, 4x16 0.6/1 kV
Overall diameter 25.5 mm, about 1,270 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Filler | PP | 16.7 | |
| Inner covering / bedding | PVC | 1.0 | 18.7 |
| Sheath | PVC | 1.2 | 21.1 |
| Tape armour | Steel | 0.40 | 21.9 |
| Sheath | PVC | 1.8 | 25.5 |
NYY-G on a drum
The smallest drum that passes every check, for 25.5 mm and about 1,270 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 9 | 779–800 kg |
| 1,000 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 10 of 13 | 1,546–1,579 kg |
Barrel at least 15 × OD = 382 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NYY-G
NYY-G belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables
Terms on this page: oversheath (outer sheath)
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro