NYY-G

NYY-G is a TIS 11 type names (Thailand) cable designation: NYY-G = NYY-G: Thai NYY (PVC insulation, PVC inner and outer sheath) with a green-and-yellow protective earth core; NYY-G = NYY-G (Thailand): PVC-insulated copper cores, PVC inner and outer sheath, with a green-and-yellow earth core. 300/500 V (60227 IEC 10) or 450/750 V (Part 101), 70 C (Thai Cable Wires). TIS 11 Part 4-2553 (60227 IEC 10, to 35 mm2, 300/500 V) and TIS 11 Part 101-2553 (NYY-G, 450/750 V).

3 coding systems recognise this code

TIS 11 type names (Thailand)

SymbolMeaning
NYY-GNYY-G: Thai NYY (PVC insulation, PVC inner and outer sheath) with a green-and-yellow protective earth core
NYY-GNYY-G (Thailand): PVC-insulated copper cores, PVC inner and outer sheath, with a green-and-yellow earth core. 300/500 V (60227 IEC 10) or 450/750 V (Part 101), 70 C (Thai Cable Wires). TIS 11 Part 4-2553 (60227 IEC 10, to 35 mm2, 300/500 V) and TIS 11 Part 101-2553 (NYY-G, 450/750 V)

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC)
YPolyvinyl Chloride (PVC)
GHelical Galvanized Steel Tape

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General
GRubber / Elastomer Insulation Or Sheath (Older Editions: Natural Rubber NR Or SBR)

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NYY-G as the cable designer builds it, 4x16 0.6/1 kV

Overall diameter 25.5 mm, about 1,270 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
FillerPP16.7
Inner covering / beddingPVC1.018.7
SheathPVC1.221.1
Tape armourSteel0.4021.9
SheathPVC1.825.5

NYY-G on a drum

The smallest drum that passes every check, for 25.5 mm and about 1,270 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 9779–800 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG10 of 131,546–1,579 kg

Barrel at least 15 × OD = 382 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NYY-G

NYY-G belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables

Terms on this page: oversheath (outer sheath)

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NYY-G

Related cables

More TIS 11 type names (Thailand) designations