NYM-JZ

NYM-JZ is a DIN VDE type names (Germany) cable designation: N = German national (VDE) type; Y = PVC insulation TI1 (DIN VDE 0281-1): 0,6 mm at 1,5 mm², 0,7 at 2,5, 0,8 at 4 and 6, 1,0 at 10 and 16, 1,2 at 25 and 35 mm² (DIN VDE 0250-204 Table 1); M = Sheath of PVC TM1 (DIN VDE 0281-1), 1,4 to 1,8 mm, over a common covering that fills the gaps, 0,4 to 1,2 mm (a guide value; none on a single core) (DIN VDE 0250-204 5.6, 5.7, Table 1); NYM = NYM: PVC installation cable (Mantelleitung) for fixed installation, the type of DIN VDE 0250-204. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-204:2000-12 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1 columns 7 and 8, e.g. 3 x 1,5 mm²: 8,2 to 9,9 mm, 5 x 2,5 mm²: 11,0 to 13,3 mm; tests, Table 2: 2 kV a.c. for 5 min on the complete cable).

2 coding systems recognise this code

DIN VDE type names (Germany)

SymbolMeaning
NGerman national (VDE) type
YPVC insulation TI1 (DIN VDE 0281-1): 0,6 mm at 1,5 mm², 0,7 at 2,5, 0,8 at 4 and 6, 1,0 at 10 and 16, 1,2 at 25 and 35 mm² (DIN VDE 0250-204 Table 1)
MSheath of PVC TM1 (DIN VDE 0281-1), 1,4 to 1,8 mm, over a common covering that fills the gaps, 0,4 to 1,2 mm (a guide value; none on a single core) (DIN VDE 0250-204 5.6, 5.7, Table 1)
NYMNYM: PVC installation cable (Mantelleitung) for fixed installation, the type of DIN VDE 0250-204. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-204:2000-12 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1 columns 7 and 8, e.g. 3 x 1,5 mm²: 8,2 to 9,9 mm, 5 x 2,5 mm²: 11,0 to 13,3 mm; tests, Table 2: 2 kV a.c. for 5 min on the complete cable)

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General
MSheathed Installation Cable, Medium Mechanical Stress (Mantelleitung, E.g. NYM)
-JZWith Green/Yellow Earth Core, Other Cores Numbered (White Numbers On Black)

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

What is NYM cable?

NYM: PVC installation cable (Mantelleitung) for fixed installation, the type of DIN VDE 0250-204. Rating: U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). Standard: DIN VDE 0250-204:2000-12 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1 columns 7 and 8, e.g. 3 x 1,5 mm²: 8,2 to 9,9 mm, 5 x 2,5 mm²: 11,0 to 13,3 mm; tests, Table 2: 2 kV a.c. for 5 min on the complete cable).

NYM-J has a green-and-yellow core, NYM-O none (3.2). The letter reading below this row is the DIN VDE 0250 letter code; this row is the type as the standard defines it.

Documents and pages the readings were taken from

  • DIN VDE 0250-204:2000-12 (clauses 3 to 7 p. 4 to 6, Table 1 and Table 2)

DIN VDE type names (Germany): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Work with NYM-JZ

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More DIN VDE type names (Germany) designations

NYM-JZ