NYM-J 3x1,5

NYM-J 3x1,5 is a DIN VDE type names (Germany) cable designation: N = German national (VDE) type; Y = PVC insulation TI1 (DIN VDE 0281-1): 0,6 mm at 1,5 mm², 0,7 at 2,5, 0,8 at 4 and 6, 1,0 at 10 and 16, 1,2 at 25 and 35 mm² (DIN VDE 0250-204 Table 1); M = Sheath of PVC TM1 (DIN VDE 0281-1), 1,4 to 1,8 mm, over a common covering that fills the gaps, 0,4 to 1,2 mm (a guide value; none on a single core) (DIN VDE 0250-204 5.6, 5.7, Table 1); 3X1,5 = 1.5 mm², 3 cores, one of them green-yellow (protective); -J = With Earthing Core (Green/Yellow Core); NYM = NYM: PVC installation cable (Mantelleitung) for fixed installation, the type of DIN VDE 0250-204. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-204:2000-12 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1 columns 7 and 8, e.g. 3 x 1,5 mm²: 8,2 to 9,9 mm, 5 x 2,5 mm²: 11,0 to 13,3 mm; tests, Table 2: 2 kV a.c. for 5 min on the complete cable).

2 coding systems recognise this code

DIN VDE type names (Germany)

SymbolMeaning
NGerman national (VDE) type
YPVC insulation TI1 (DIN VDE 0281-1): 0,6 mm at 1,5 mm², 0,7 at 2,5, 0,8 at 4 and 6, 1,0 at 10 and 16, 1,2 at 25 and 35 mm² (DIN VDE 0250-204 Table 1)
MSheath of PVC TM1 (DIN VDE 0281-1), 1,4 to 1,8 mm, over a common covering that fills the gaps, 0,4 to 1,2 mm (a guide value; none on a single core) (DIN VDE 0250-204 5.6, 5.7, Table 1)
3X1,51.5 mm², 3 cores, one of them green-yellow (protective)
-JWith Earthing Core (Green/Yellow Core)
NYMNYM: PVC installation cable (Mantelleitung) for fixed installation, the type of DIN VDE 0250-204. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-204:2000-12 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1 columns 7 and 8, e.g. 3 x 1,5 mm²: 8,2 to 9,9 mm, 5 x 2,5 mm²: 11,0 to 13,3 mm; tests, Table 2: 2 kV a.c. for 5 min on the complete cable)

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General
MSheathed Installation Cable, Medium Mechanical Stress (Mantelleitung, E.g. NYM)
-JWith Earthing Core (Green/Yellow Core)

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

What is NYM cable?

NYM: PVC installation cable (Mantelleitung) for fixed installation, the type of DIN VDE 0250-204. Rating: U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). Standard: DIN VDE 0250-204:2000-12 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1 columns 7 and 8, e.g. 3 x 1,5 mm²: 8,2 to 9,9 mm, 5 x 2,5 mm²: 11,0 to 13,3 mm; tests, Table 2: 2 kV a.c. for 5 min on the complete cable).

NYM-J has a green-and-yellow core, NYM-O none (3.2). The letter reading below this row is the DIN VDE 0250 letter code; this row is the type as the standard defines it.

Documents and pages the readings were taken from

  • DIN VDE 0250-204:2000-12 (clauses 3 to 7 p. 4 to 6, Table 1 and Table 2)

DIN VDE type names (Germany): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NYM-J 3x1,5: equivalents in other countries

Shown for 3x1.5 300/500 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)60227 IEC 10 (IEC 60227-4)60227 IEC 10 3G1,5 300/500 VCloseInsulation 0.6 → 0.7 mm; Sheath 1.4 → 1.2 mm
ChinaGB/T 9330KVV 3x1.5 450/750 VCloserated higher: 450/750 V (this cable 300/500 V); Insulation 0.6 → 0.7 mm; Inner covering / bedding material: not in the equivalent; Sheath 1.4 → 1.2 mm

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

NYM-J 3x1,5 as the cable designer builds it, 3x1.5 300/500 V

Overall diameter 9.2 mm, about 130 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.602.6
FillerPVC5.6
Inner covering / beddingPVC0.406.4
SheathPVC1.49.2

NYM-J 3x1,5 on a drum

The smallest drum that passes every check, for 9.2 mm and about 130 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1472 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG15 of 17161–165 kg

Barrel at least 15 × OD = 137 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NYM-J 3x1,5

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NYM-J 3x1,5

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More DIN VDE type names (Germany) designations

NYM-J 3x1,5