LI2YCY

LI2YCY is a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable designation: Li = Stranded Conductor, Flexible (Litzenleiter To VDE 0812); 2Y = Polyethylene (PE); C = Copper Screen As Braid; Y = Polyvinyl Chloride (PVC).

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: HD 627 S1:1996/A2:2005: Multicore and multipair cables for installation above and below ground; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of LI2YCY 4x0.5 500 V:

  • LI2YCY: Li = Stranded Conductor, Flexible (Litzenleiter To VDE 0812); 2Y = Polyethylene (PE); C = Copper Screen As Braid; Y = Polyvinyl Chloride (PVC)
  • 4x0.5 500 V: 4 cores, each copper 0.5 mm²; rated voltage peak500 kV

Related cable types: Li2YCYv · LI2YCY-TP · Li2YCYv-TP · Li2ycy Pimf · Li2ycy Pimf lf

VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888)

SymbolMeaning
LiStranded Conductor, Flexible (Litzenleiter To VDE 0812)
2YPolyethylene (PE)
CCopper Screen As Braid
YPolyvinyl Chloride (PVC)

How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
LiEquipment Wire With Fine Stranded Conductor
2YPolyethylene (PE)
CShielded
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code

A VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 125 symbols for this system.

What does Li mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? Li means Stranded Conductor, Flexible (Litzenleiter To VDE 0812).

What does 2Y mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? 2Y means Polyethylene (PE).

What does C mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? C means Copper Screen As Braid; or Jute Serving With Compound.

What does Y mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? Y means Polyvinyl Chloride (PVC).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

LI2YCY as the cable designer builds it, 4x0.5 500 V

Overall diameter 6.2 mm, about 60 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPE0.451.8
Separation tapePolyester0.054.4
Braid (copper wires)Copper0.204.8
SheathPVC0.706.2

LI2YCY on a drum

The smallest drum that passes every check, for 6.2 mm and about 60 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 3 (390 mm flange), plastic KTG drums (Europe), KTG13 of 1432 kg
1,000 mKTG 5 (500 mm flange), plastic KTG drums (Europe), Bayka, KTG20 of 2163–64 kg

Barrel at least 20 × OD = 125 mm for a cable of this kind (Telecom, data and control cable): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: LI2YCY

LI2YCY belongs to the family Control and instrument cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Control and instrument cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with LI2YCY

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) designations

LI2YCY