LI2YCY
LI2YCY is a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable designation: Li = Stranded Conductor, Flexible (Litzenleiter To VDE 0812); 2Y = Polyethylene (PE); C = Copper Screen As Braid; Y = Polyvinyl Chloride (PVC).
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: HD 627 S1:1996/A2:2005: Multicore and multipair cables for installation above and below ground; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of LI2YCY 4x0.5 500 V:
LI2YCY: Li = Stranded Conductor, Flexible (Litzenleiter To VDE 0812); 2Y = Polyethylene (PE); C = Copper Screen As Braid; Y = Polyvinyl Chloride (PVC)4x0.5 500 V: 4 cores, each copper 0.5 mm²; rated voltage peak500 kV
Related cable types: Li2YCYv · LI2YCY-TP · Li2YCYv-TP · Li2ycy Pimf · Li2ycy Pimf lf
VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888)
| Symbol | Meaning |
|---|---|
Li | Stranded Conductor, Flexible (Litzenleiter To VDE 0812) |
2Y | Polyethylene (PE) |
C | Copper Screen As Braid |
Y | Polyvinyl Chloride (PVC) |
How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code
DIN VDE 0250 cords, control and special cables (Germany)
| Symbol | Meaning |
|---|---|
Li | Equipment Wire With Fine Stranded Conductor |
2Y | Polyethylene (PE) |
C | Shielded |
Y | Polyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General |
How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code
How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code
A VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 125 symbols for this system.
What does Li mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? Li means Stranded Conductor, Flexible (Litzenleiter To VDE 0812).
What does 2Y mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? 2Y means Polyethylene (PE).
What does C mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? C means Copper Screen As Braid; or Jute Serving With Compound.
What does Y mean in a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code? Y means Polyvinyl Chloride (PVC).
Fire behaviour (EU CPR)
PVC sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
LI2YCY as the cable designer builds it, 4x0.5 500 V
Overall diameter 6.2 mm, about 60 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PE | 0.45 | 1.8 |
| Separation tape | Polyester | 0.05 | 4.4 |
| Braid (copper wires) | Copper | 0.20 | 4.8 |
| Sheath | PVC | 0.70 | 6.2 |
LI2YCY on a drum
The smallest drum that passes every check, for 6.2 mm and about 60 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 3 (390 mm flange), plastic KTG drums (Europe), KTG | 13 of 14 | 32 kg |
| 1,000 m | KTG 5 (500 mm flange), plastic KTG drums (Europe), Bayka, KTG | 20 of 21 | 63–64 kg |
Barrel at least 20 × OD = 125 mm for a cable of this kind (Telecom, data and control cable): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: LI2YCY
LI2YCY belongs to the family Control and instrument cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Control and instrument cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with LI2YCY
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) designations