HEPRZ1
HEPRZ1 is a UNE (Spain: UNE 21123 / UNE 20434) cable designation: HEPR = Hard Grade Ethylene-Propylene Rubber (HEPR); Z1 = Low Smoke Zero Halogen Compound.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of HEPRZ1 1x240/16 12/20 kV:
HEPRZ1: HEPR = Hard Grade Ethylene-Propylene Rubber (HEPR); Z1 = Low Smoke Zero Halogen Compound1x240/16 12/20 kV: one core, copper 240 mm²; rated voltage 12/20 kV
Related cable types: herpz1
UNE (Spain: UNE 21123 / UNE 20434)
| Symbol | Meaning |
|---|---|
HEPR | Hard Grade Ethylene-Propylene Rubber (HEPR) |
Z1 | Low Smoke Zero Halogen Compound |
NEN 3207 / KEMA (Netherlands)
| Symbol | Meaning |
|---|---|
H | Chlorinated Or Chlorosulphonated Polyethylene (CPE / CSM) |
E | Polyethylene (PE) |
P | Paper Insulation |
R | Vulcanised Rubber (Natural, SBR Or EPR, 60 °C) |
Z1 | Low Smoke Zero Halogen Compound |
How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code
A UNE (Spain: UNE 21123 / UNE 20434) designation (Spain) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 56 symbols for this system.
What does HEPR mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? HEPR means Hard Grade Ethylene-Propylene Rubber (HEPR).
What does Z1 mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? Z1 means Low Smoke Zero Halogen Compound.
Fire behaviour (EU CPR)
Halogen-free compound (Z1). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
HEPRZ1: equivalents in other countries
Shown for 1x240/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | Cu/HEPR/CWS/LSZH 1x240/16 12/20 kV (to IEC 60502-2) | Close | Conductor screen (semicon) 0.5 → 0.6 mm; Insulation 4.2 → 5.5 mm; Insulation screen (semicon) 0.5 → 0.8 mm; Sheath 3 → 2.1 mm; this cable as built misses 1 of its rules |
| Italy | HD 620 S3 9-I | no letters for this build | Close | Conductor screen (semicon) 0.5 → 0.6 mm; Insulation 4.2 → 5.5 mm; Insulation screen (semicon) 0.5 → 0.8 mm; Wire screen section 16 → 6 mm²; this cable as built misses 1 of its rules |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
HEPRZ1 as the cable designer builds it, 1x240/16 12/20 kV
Overall diameter 36.4 mm, about 3,300 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.50 | 19.4 |
| Insulation | HEPR | 4.2 | 27.8 |
| Insulation screen (semicon) | Semiconducting | 0.50 | 28.8 |
| Wire screen | Copper | 42 × 0.70 | 30.4 |
| Sheath | Halogen-free (LSZH) | 3.0 | 36.4 |
HEPRZ1 on a drum
The smallest drum that passes every check, for 36.4 mm and about 3,300 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 10 | 1,991–2,063 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 9 | 3,779–3,900 kg |
Barrel at least 25 × OD = 910 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: HEPRZ1
HEPRZ1 belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Accessories for this cable
Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).
- Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
- Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
- Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
- Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
- Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
- Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²
Typical; no maker or kit is named, and your kit's own sheet decides.
Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro