EXVB
EXVB is a NBN type names (Belgium) cable designation: E = Energy Cable; X = Cross-linked polyethylene (XLPE) insulation; V = PVC outer sheath; B = Belgium Type; EXVB = EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of EXVB 4x16 0.6/1 kV:
EXVB: E = Energy Cable; X = Cross-linked polyethylene (XLPE) insulation; V = PVC outer sheath; B = Belgium Type; EXVB = EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC4x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV
NBN type names (Belgium)
| Symbol | Meaning |
|---|---|
E | Energy Cable |
X | Cross-linked polyethylene (XLPE) insulation |
V | PVC outer sheath |
B | Belgium Type |
EXVB | EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC |
NBN (Belgian national cable names, ...B types)
| Symbol | Meaning |
|---|---|
E | Energy Cable |
X | Cross-Linked Polyethylene (XLPE) |
V | Polyvinyl Chloride (PVC) |
B | Belgium Type |
How to read a NBN (Belgian national cable names, ...B types) cable code
What is EXVB cable?
EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. Rating: 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. Standard: NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC.
Standaardbestek 270 v3.0 (Agentschap Wegen en Verkeer, October 2016), chapter 46, 1.1.2 (p. 46-9): E energy cable, X XLPE insulation, V PVC outer sheath, B conforms to the Belgian NBN standards; NBN HD 603:2007 part 5 section A; copper class 1 round to 10 mm2, class 2 round from 16 mm2, sector from 70 mm2 in 3 and 4 core cables; common covering; black PVC sheath; HD 308 S2 colours; 90 C, 250 C for 5 s. Nexans Belgium EXVB Eca 3G1.5: solid class 1, XLPE 0,7 mm (average), PVC inner sheath 1,0 mm, outer sheath minimum 2,0 mm; 4x120: XLPE 1,2, inner sheath 1,4, outer sheath minimum 2,9 (NBN HD 603 Part 5/Sect.A, HD 603:2007/A1:2016). Buried: extra mechanical protection needed (Nexans).
Documents and pages the readings were taken from
Fire behaviour (EU CPR)
PVC sheath (V).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
EXVB: equivalents in other countries
Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | N2XY 4x16 RM 0,6/1 kV | Equivalent | every value the same |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding 1 → 1.2 mm; Sheath 1.8 → 1.7 mm; Wire armour material: only in the equivalent; Overall diameter 20.81 → 23.51 mm |
| India | IS 7098 (Part 1) | 2XY 4x16 1100 V | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 20.81 → 19.41 mm |
No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (armoured cables only, asks another sheath compound).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
EXVB as the cable designer builds it, 4x16 0.6/1 kV
Overall diameter 20.8 mm, about 890 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 15.2 | |
| Inner covering / bedding | PVC | 1.0 | 17.2 |
| Sheath | PVC | 1.8 | 20.8 |
EXVB on a drum
The smallest drum that passes every check, for 20.8 mm and about 890 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 10 of 10 | 516–523 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 13 of 13 | 1,034–1,055 kg |
Barrel at least 15 × OD = 312 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: EXVB
EXVB belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables
Terms on this page: oversheath (outer sheath)