EXVB

EXVB is a NBN type names (Belgium) cable designation: E = Energy Cable; X = Cross-linked polyethylene (XLPE) insulation; V = PVC outer sheath; B = Belgium Type; EXVB = EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of EXVB 4x16 0.6/1 kV:

  • EXVB: E = Energy Cable; X = Cross-linked polyethylene (XLPE) insulation; V = PVC outer sheath; B = Belgium Type; EXVB = EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC
  • 4x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV

NBN type names (Belgium)

SymbolMeaning
EEnergy Cable
XCross-linked polyethylene (XLPE) insulation
VPVC outer sheath
BBelgium Type
EXVBEXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC

NBN (Belgian national cable names, ...B types)

SymbolMeaning
EEnergy Cable
XCross-Linked Polyethylene (XLPE)
VPolyvinyl Chloride (PVC)
BBelgium Type

How to read a NBN (Belgian national cable names, ...B types) cable code

What is EXVB cable?

EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. Rating: 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. Standard: NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC.

Standaardbestek 270 v3.0 (Agentschap Wegen en Verkeer, October 2016), chapter 46, 1.1.2 (p. 46-9): E energy cable, X XLPE insulation, V PVC outer sheath, B conforms to the Belgian NBN standards; NBN HD 603:2007 part 5 section A; copper class 1 round to 10 mm2, class 2 round from 16 mm2, sector from 70 mm2 in 3 and 4 core cables; common covering; black PVC sheath; HD 308 S2 colours; 90 C, 250 C for 5 s. Nexans Belgium EXVB Eca 3G1.5: solid class 1, XLPE 0,7 mm (average), PVC inner sheath 1,0 mm, outer sheath minimum 2,0 mm; 4x120: XLPE 1,2, inner sheath 1,4, outer sheath minimum 2,9 (NBN HD 603 Part 5/Sect.A, HD 603:2007/A1:2016). Buried: extra mechanical protection needed (Nexans).

Documents and pages the readings were taken from

NBN type names (Belgium): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

EXVB: equivalents in other countries

Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)N2XY 4x16 RM 0,6/1 kVEquivalentevery value the same
South AfricaSANS 1507-4no letters for this buildCloseInner covering / bedding 1 → 1.2 mm; Sheath 1.8 → 1.7 mm; Wire armour material: only in the equivalent; Overall diameter 20.81 → 23.51 mm
IndiaIS 7098 (Part 1)2XY 4x16 1100 VCloserated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 20.81 → 19.41 mm

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

EXVB as the cable designer builds it, 4x16 0.6/1 kV

Overall diameter 20.8 mm, about 890 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP15.2
Inner covering / beddingPVC1.017.2
SheathPVC1.820.8

EXVB on a drum

The smallest drum that passes every check, for 20.8 mm and about 890 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG10 of 10516–523 kg
1,000 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG13 of 131,034–1,055 kg

Barrel at least 15 × OD = 312 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: EXVB

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 96 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.6 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

EXVB belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables

Terms on this page: oversheath (outer sheath)