XGB

XGB is a NBN type names (Belgium) cable designation: X = Cross-linked polyethylene (XLPE) insulation; G = LSZH (Low Smoke Zero Halogen Compund) Outersheath; B = Belgium Type; XGB = XGB: Belgian halogen-free 0,6/1 kV installation cable, copper conductors in XLPE insulation, a halogen-free common covering and a green halogen-free outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 604 Part 5 Section L (Standaardbestek 270; Nexans Belgium), CEBEC.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of XGB 3x16 0.6/1 kV:

  • XGB: X = Cross-linked polyethylene (XLPE) insulation; G = LSZH (Low Smoke Zero Halogen Compund) Outersheath; B = Belgium Type; XGB = XGB: Belgian halogen-free 0,6/1 kV installation cable, copper conductors in XLPE insulation, a halogen-free common covering and a green halogen-free outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 604 Part 5 Section L (Standaardbestek 270; Nexans Belgium), CEBEC
  • 3x16 0.6/1 kV: 3 cores, each copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: XGB-F2 · NA2XGBY · XGB Cca-s1,d2,a1

NBN type names (Belgium)

SymbolMeaning
XCross-linked polyethylene (XLPE) insulation
GLSZH (Low Smoke Zero Halogen Compund) Outersheath
BBelgium Type
XGBXGB: Belgian halogen-free 0,6/1 kV installation cable, copper conductors in XLPE insulation, a halogen-free common covering and a green halogen-free outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 604 Part 5 Section L (Standaardbestek 270; Nexans Belgium), CEBEC

NBN (Belgian national cable names, ...B types)

SymbolMeaning
XCross-Linked Polyethylene (XLPE)
GLow Smoke Zero Halogen Compound
BBelgium Type

How to read a NBN (Belgian national cable names, ...B types) cable code

What is XGB cable?

XGB: Belgian halogen-free 0,6/1 kV installation cable, copper conductors in XLPE insulation, a halogen-free common covering and a green halogen-free outer sheath. Rating: 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. Standard: NBN HD 604 Part 5 Section L (Standaardbestek 270; Nexans Belgium), CEBEC.

Standaardbestek 270 v3.0 chapter 46, 1.1.6 (p. 46-12): X XLPE insulation, G halogen-free outer sheath, B conforms to the Belgian NBN standards; NBN HD 604 part 5 section L; green halogen-free thermoplastic sheath; NBN C 30-004 F1, F2, SD, SA. Nexans Belgium XGB Cca 4x50: bare copper class 1, stranded class 2 from 16 mm2, XLPE, halogen-free compound or tape, halogen-free polyolefin sheath, green; 0,6/1 kV; test 4 kV. G is the halogen-free (LSOH) letter of the NBN installation key (Cebeo Tome 04 2011 p. 24).

Documents and pages the readings were taken from

NBN type names (Belgium): how to read the cable type names

Fire behaviour (EU CPR)

  • Halogen-free compound (G, XGB). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

XGB: equivalents in other countries

Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)N2XH 3x16 RM 0,6/1 kVEquivalentevery value the same
IndiaIS 7098 (Part 1)2XZ 3x16 1100 V (the code letters of IS 7098 (Part 1):2025 cl. 18.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 19.17 → 17.77 mm
South AfricaSANS 1507-4no letters for this buildCloseInner covering / bedding material LSZH → PVC; Inner covering / bedding 1 → 0.8 mm; Sheath material LSZH → PVC; Sheath 1.8 → 1.6 mm

No equivalent in: BS 5467 (armoured cables only, asks another sheath compound); BS 6724 (armoured cables only); BS 7846 (armoured cables only).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

XGB as the cable designer builds it, 3x16 0.6/1 kV

Overall diameter 19.2 mm, about 720 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP13.6
Inner covering / beddingHalogen-free (LSZH)1.015.6
SheathHalogen-free (LSZH)1.819.2

XGB on a drum

The smallest drum that passes every check, for 19.2 mm and about 720 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 11431–438 kg
1,000 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG12 of 14864–885 kg

Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: XGB

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 96 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.6 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

XGB belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables

Terms on this page: oversheath (outer sheath)