CU/XLPE/CWS/LEAD/HDPE

CU/XLPE/CWS/LEAD/HDPE is a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable designation: CU = Copper Conductor; XLPE = Cross-Linked Polyethylene (XLPE); CWS = Copper Wire Screen (concentric copper wires); LEAD = Lead Sheath; HDPE = High Density Polyethylene (HDPE).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60840:2020+AMD1:2023: Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) - Test methods and requirements; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of CU/XLPE/CWS/LEAD/HDPE 1x630/95 64/110 kV:

  • CU/XLPE/CWS/LEAD/HDPE: CU = Copper Conductor; XLPE = Cross-Linked Polyethylene (XLPE); CWS = Copper Wire Screen (concentric copper wires); LEAD = Lead Sheath; HDPE = High Density Polyethylene (HDPE)
  • 1x630/95 64/110 kV: one core, copper 630 mm²; rated voltage 64/110 kV

Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice)

SymbolMeaning
CUCopper Conductor
XLPECross-Linked Polyethylene (XLPE)
CWSCopper Wire Screen (concentric copper wires)
LEADLead Sheath
HDPEHigh Density Polyethylene (HDPE)

How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code

How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code

A Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designation (UK / International) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 119 symbols for this system.

What does CU mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? CU means Copper Conductor.

What does XLPE mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? XLPE means Cross-Linked Polyethylene (XLPE).

What does CWS mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? CWS means Copper Wire Screen (concentric copper wires).

What does LEAD mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? LEAD means Lead Sheath.

What does HDPE mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? HDPE means High Density Polyethylene (HDPE).

Fire behaviour (EU CPR)

  • PE sheath (HDPE).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

CU/XLPE/CWS/LEAD/HDPE as the cable designer builds it, 1x630/95 64/110 kV

Overall diameter 82.6 mm, about 15,440 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting1.233.0
InsulationXLPE16.065.0
Insulation screen (semicon)Semiconducting1.067.0
Swelling tape (water block)Swelling0.5068.0
Wire screenCopper247 × 0.7069.6
Swelling tape (water block)Swelling0.5070.6
Metal sheath (lead or smooth aluminium)Lead alloy2.074.6
SheathPE4.082.6

CU/XLPE/CWS/LEAD/HDPE on a drum

The smallest drum that passes every check, for 82.6 mm and about 15,440 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 87 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.
1,000 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.

Barrel at least 25 × OD = 2,065 mm for a cable of this kind (High voltage (above 36 kV)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: CU/XLPE/CWS/LEAD/HDPE

CU/XLPE/CWS/LEAD/HDPE belongs to the family High voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: High voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with CU/XLPE/CWS/LEAD/HDPE

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designations

CU/XLPE/CWS/LEAD/HDPE