BFQB
BFQB is a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable designation: B = Fire Resistant Tape + Insulation (Halogen-Free); F = Bedding Or Taping (Halogen-Free); Q = Steel Wires + Counter Steel Tape (Optional); B = Hydrocarbon Resistant Sheath.
3 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of BFQB 3x95/25 12/20 kV:
BFQB: B = Fire Resistant Tape + Insulation (Halogen-Free); F = Bedding Or Taping (Halogen-Free); Q = Steel Wires + Counter Steel Tape (Optional); B = Hydrocarbon Resistant Sheath3x95/25 12/20 kV: 3 cores, each aluminium 95 mm²; rated voltage 12/20 kV
Norwegian type designation (NEK 606 offshore and Norwegian land cables)
| Symbol | Meaning |
|---|---|
B | Fire Resistant Tape + Insulation (Halogen-Free) |
F | Bedding Or Taping (Halogen-Free) |
Q | Steel Wires + Counter Steel Tape (Optional) |
B | Hydrocarbon Resistant Sheath |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
NEN 3207 / KEMA (Netherlands)
| Symbol | Meaning |
|---|---|
B | Ethylene-Propylene Rubber (EPR) |
F | Fine-Wired In Flexible Cables-Class 5 |
Q | Polyurethane (PUR) |
B | Ethylene-Propylene Rubber (EPR) |
SS 424 17 01 (Sweden)
| Symbol | Meaning |
|---|---|
B | Low Smoke, Zero Halogen Thermoplastic Polyolefin |
F | Copper Screen As Braid |
Q | Low Smoke, Zero Halogen Thermoplastic Polyolefin |
B | Aluminium Alloy Conductor |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
A Norwegian type designation (NEK 606 offshore and Norwegian land cables) designation (Norway) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 95 symbols for this system.
What does B mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? B means Fire Resistant Tape + Insulation (Halogen-Free); or Corrugated Aluminium (optionally with corrosion protection); or Steel Tapes, 2 Off; or Hydrocarbon Resistant Sheath.
What does F mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? F means PE Or PP + Filling Compound; or Bedding Or Taping (Halogen-Free); or Flat Steel Wire Armour; or Semi-Conducting PE.
What does Q mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? Q means Fibre in Loose Tube (Nexans Norway power-cable key: PVC + additional layer); or Steel Wires + Counter Steel Tape (Optional).
Fire behaviour (EU CPR)
Halogen-free compound (B, F). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
Fire resistant (B): the circuit keeps working in a fire. That is circuit integrity, classified apart from reaction to fire (EN 13501-3: P and PH classes, 15 to 120 min). It gives no reaction-to-fire class; that one is declared on its own.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Not equivalent, because
IEC 60331 ≠ BS 6387 (C, W, Z) ≠ BS 8491 ≠ EN 50200 (PH) ≠ DIN 4102-12 (E30, E60, E90) ≠ UL 2196
Not equivalent, because Flame or furnace, temperature, mechanical shock, water and what is tested (a cable alone, or a cable with its supports) all differ: a time or class from one test says nothing about another.
IEC 60331
- Parts 1 and 2: a flame of at least 830 °C with mechanical shock; part 1 for cables over 20 mm, part 2 up to 20 mm; up to 0.6/1 kV. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)
- Parts 11 and 21: fire alone, at least 750 °C. Sources: IEC 60331-11:1999+A1:2009 (edition 1.1), 5.2 p. 7, Annex A p. 13; IEC 60331-21:1999, cl. 7 and 8, pp. 13 to 15 (read in the standard)
- Pass: the circuit keeps working for the stated time. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)
BS 6387 (C, W, Z)
- C: 950 °C for 3 h. W: 650 °C for 15 min, then 15 min with water. Z: 950 °C with a shock every 30 s for 15 min. CWZ: all three passed. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (read in the standard)
- Cables up to 600/1000 V and 20 mm diameter. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (read in the standard)
BS 8491
- Cables over 20 mm: 842 °C with impact and a water jet; classes F30, F60, F120. Sources: BSI listing of BS 8491:2008 and summaries of it (quoted by others)
EN 50200 (PH)
- 830 °C with a shock every 5 min, cables up to 20 mm; Annex E adds a water spray. Sources: BS EN 50200:2015, 6.3 (830 °C, +40 / 0), 8.3 (shock every 5 min), clause 1 (cables up to 20 mm), Annex D (PH classes), Annex E (water spray) (read in the standard)
- Classes PH15, PH30, PH60, PH90, PH120 (EN 13501-3). Sources: EN 13501-3:2005+A1:2009 with draft A2 (cover September 2013), cl 4.3 p. 7; cl 6.3 p. 9; cl 7.2.4.4, 7.2.5.4 pp. 16-17; cl 7.2.6.2 p. 18 (read in a draft); BS EN 50200:2015, 6.3 (830 °C, +40 / 0), 8.3 (shock every 5 min), clause 1 (cables up to 20 mm), Annex D (PH classes), Annex E (water spray) (read in the standard)
DIN 4102-12 (E30, E60, E90)
- The cable with its supports in a furnace on the standard temperature curve, at up to 400 V; E30, E60 and E90 hold only for the support system tested. Sources: Datwyler (N)HXCH FE180 E90 datasheet (maker's catalogue)
UL 2196
- A furnace on the ASTM E119 time-temperature curve (NFPA 262 Annex A names it for UL 2196). Sources: NFPA 262:2023 (NFPA free access), Annex A, A.1.1.1 (read in the standard)
- Ratings up to 2 h, with a hose stream after the fire. Sources: research: equivalents map F5 (UL 2196 not read) (typical practice)
BFQB as the cable designer builds it, 3x95/25 12/20 kV
Overall diameter 60.7 mm, about 3,410 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.60 | 12.7 |
| Insulation | XLPE | 5.1 | 22.9 |
| Insulation screen (semicon) | Semiconducting | 0.60 | 24.1 |
| Filler | Semiconducting | 51.9 | |
| Inner covering / bedding | Semiconducting | 0.60 | 53.1 |
| Wire screen | Copper | 65 × 0.70 | 54.7 |
| Sheath | Halogen-free (LSZH) | 3.0 | 60.7 |
BFQB on a drum
The smallest drum that passes every check, for 60.7 mm and about 3,410 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 64 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG | 5 of 7 | 2,880–2,945 kg |
| 1,000 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
Barrel at least 20 × OD = 1,215 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: BFQB
BFQB belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables
Terms on this page: bedding
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Accessories for this cable
Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).
- Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
- Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
- Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
- Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
- Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
The kits are single core: on this three core cable one goes on each core.
Typical; no maker or kit is named, and your kit's own sheet decides.
Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro
Work with BFQB
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More Norwegian type designation (NEK 606 offshore and Norwegian land cables) designations