AXAL-TT

AXAL-TT is a SS 424 17 01 (Sweden) cable designation: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); A = Screen Of Aluminium Foil And/Or Aluminium Wire; L = Polyethylene (PE); TT = Transversely And Longitudinally Water-Tight Construction.

3 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of AXAL-TT 3x95/25 12/20 kV:

  • AXAL-TT: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); A = Screen Of Aluminium Foil And/Or Aluminium Wire; L = Polyethylene (PE); TT = Transversely And Longitudinally Water-Tight Construction
  • 3x95/25 12/20 kV: 3 cores, each aluminium 95 mm²; rated voltage 12/20 kV

Related cable types: AXAL

SS 424 17 01 (Sweden)

SymbolMeaning
AAluminium Conductor
XCross-Linked Polyethylene (XLPE, PEX)
AScreen Of Aluminium Foil And/Or Aluminium Wire
LPolyethylene (PE)
TTTransversely And Longitudinally Water-Tight Construction

How to read a SS 424 17 01 (Sweden) cable code

China (GB / JB/T / MT cable model codes)

SymbolMeaning
ATwin Cable
XNatural Or Styrene-Butadiene Rubber
AAluminium Foil With Polyethylene Sheath
LAluminium Conductor
TCopper Conductor
TCopper Conductor

How to read a China (GB / JB/T / MT cable model codes) cable code

CEI-UNEL 35011 (Italy)

SymbolMeaning
AAluminium Conductor
XHelically Bundled Visible Cores
AAluminium Sheath, Pressed Or Welded, Smooth
LAlloyed Lead Sheath For General Use
TOne Or More Mica Glass Tapes, Or A Closed Glass Braid
TOne Or More Mica Glass Tapes, Or A Closed Glass Braid

How to read a CEI-UNEL 35011 (Italy) cable code

How to read a SS 424 17 01 (Sweden) cable code

A SS 424 17 01 (Sweden) designation (Sweden) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 90 symbols for this system.

What does A mean in a SS 424 17 01 (Sweden) cable code? A means Aluminium Conductor; or Screen Of Aluminium Foil And/Or Aluminium Wire.

What does X mean in a SS 424 17 01 (Sweden) cable code? X means Cross-Linked Polyethylene (XLPE, PEX); or Polyvinyl Chloride (PVC), Oval Section; or Without Protective Conductor (Size Field).

What does L mean in a SS 424 17 01 (Sweden) cable code? L means Polyethylene (PE); or Screen Of Plastic-Coated Aluminium Tape (Possibly With A Copper Screen); Or Polyethylene (PE) Sheath.

What does TT mean in a SS 424 17 01 (Sweden) cable code? TT means Transversely And Longitudinally Water-Tight Construction.

Fire behaviour (EU CPR)

  • PE sheath (L).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

AXAL-TT: equivalents in other countries

Shown for 3x95/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
NorwayHD 620 S3 10-Kno letters for this buildEquivalentInsulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 59.53 → 60.39 mm
DenmarkHD 620 S3 10-DPEX-AL 3x95+25 12/20 (24) kV (the letters do not say the laminate and the water block)EquivalentInsulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 2.9 mm; Overall diameter 59.53 → 61.91 mm
International (IEC)IEC 60502Al/XLPE/CWS/PE 3x95/25 12/20 kV (to IEC 60502-2)EquivalentInsulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 2.9 mm; Overall diameter 59.53 → 61.91 mm
NetherlandsHD 620 S3 10-JYMeKrvasdlwd 12/20 kV 3x95 Al rs +as35 (key read from a maker (Nedkab), the NEN text not seen)Closescreen 25 → 35 mm² (HD 620 10-J Table A.3); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 3.2 mm; Overall diameter 59.53 → 62.51 mm; this cable as built misses 2 of its rules
IndiaIS 7098 (Part 2)A2X2Y 3x95 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3)Closerated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Insulation screen (semicon) 0.6 → 0.8 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules

No equivalent in: HD 620 S3 10-C (DIN VDE 0276-620) (no three-core cable at this voltage); BS 6622 (armoured cables only, asks a screen on each core); HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change); HD 620 S3 10-G (the size, cores or voltage would change); HD 620 S3 10-L (the size, cores or voltage would change); HD 620 S3 10-N (the size, cores or voltage would change); HD 620 S3 10-O (the size, cores or voltage would change); HD 620 S3 10-P (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

AXAL-TT as the cable designer builds it, 3x95/25 12/20 kV

Overall diameter 59.5 mm, about 3,180 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6012.7
InsulationXLPE5.122.9
Insulation screen (semicon)Semiconducting0.6024.1
FillerSemiconducting51.9
Wire screenCopper65 × 0.7051.9
Inner covering / beddingSemiconducting0.6053.1
Laminate (radial water block)Aluminium0.2053.5
SheathPE3.059.5

AXAL-TT on a drum

The smallest drum that passes every check, for 59.5 mm and about 3,180 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 63 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG5 of 72,765–2,830 kg
1,000 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.

Barrel at least 20 × OD = 1,191 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: AXAL-TT

AXAL-TT belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Accessories for this cable

Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).

  • Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
  • Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
  • Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
  • Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
  • Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²

The kits are single core: on this three core cable one goes on each core.

Typical; no maker or kit is named, and your kit's own sheet decides.

Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro

Work with AXAL-TT

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More SS 424 17 01 (Sweden) designations

AXAL-TT