6945B

6945B is a BS 6004 / BS 6500 / BS 7211 type numbers (UK) cable designation: 694 = Steel wire armoured (SWA) power cable, 600/1000 V; 5 = Number of cores: 5; B = Low smoke, halogen-free (LSZH / LSF) materials; 6945B = 6945B: 5 core XLPE insulated, LSZH bedded, steel wire armoured, LSZH sheathed power cable (Cu/XLPE/LSZH/SWA/LSZH, BS 6724). 600/1000 V, 90 C maximum conductor temperature (BS 6724). BS 6724 Table 13 (5 core, stranded copper).

1 coding system recognises this code

BS 6004 / BS 6500 / BS 7211 type numbers (UK)

SymbolMeaning
694Steel wire armoured (SWA) power cable, 600/1000 V
5Number of cores: 5
BLow smoke, halogen-free (LSZH / LSF) materials
6945B6945B: 5 core XLPE insulated, LSZH bedded, steel wire armoured, LSZH sheathed power cable (Cu/XLPE/LSZH/SWA/LSZH, BS 6724). 600/1000 V, 90 C maximum conductor temperature (BS 6724). BS 6724 Table 13 (5 core, stranded copper)

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

6945B as the cable designer builds it, 5x16 0.6/1 kV

Overall diameter 25.6 mm, about 1,720 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP17.0
Inner covering / beddingHalogen-free (LSZH)1.019.0
Wire armourSteel38 × 1.6022.2
SheathHalogen-free (LSZH)1.725.6

6945B on a drum

The smallest drum that passes every check, for 25.6 mm and about 1,720 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 91,004–1,025 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG10 of 131,996–2,029 kg

Barrel at least 15 × OD = 384 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: 6945B

6945B belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables