6942B
6942B is a BS 6004 / BS 6500 / BS 7211 type numbers (UK) cable designation: 694 = Steel wire armoured (SWA) power cable, 600/1000 V; 2 = Number of cores: 2; B = Low smoke, halogen-free (LSZH / LSF) materials; 6942B = 6942B: 2 core XLPE insulated, LSZH bedded, steel wire armoured, LSZH sheathed power cable (Cu/XLPE/LSZH/SWA/LSZH, BS 6724). 600/1000 V, 90 C maximum conductor temperature (BS 6724). BS 6724 Table 6 (2 core, stranded copper).
1 coding system recognises this code
BS 6004 / BS 6500 / BS 7211 type numbers (UK)
| Symbol | Meaning |
|---|---|
694 | Steel wire armoured (SWA) power cable, 600/1000 V |
2 | Number of cores: 2 |
B | Low smoke, halogen-free (LSZH / LSF) materials |
6942B | 6942B: 2 core XLPE insulated, LSZH bedded, steel wire armoured, LSZH sheathed power cable (Cu/XLPE/LSZH/SWA/LSZH, BS 6724). 600/1000 V, 90 C maximum conductor temperature (BS 6724). BS 6724 Table 6 (2 core, stranded copper) |
Fire behaviour (EU CPR)
Halogen-free compound (B, 6942B). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1,d1,a1H07Z1-K, Nexans SpainB2caAXQJ-RMF, Prysmian Sweden (12/20 kV)Cca-s1b,d1,a1RZ1FZ1-K (AS), Top CableCca-s1a,d1,a1RZ1-K (AS), Top Cable (B2ca-s1a,d1,a1 for some sizes)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
6942B as the cable designer builds it, 2x16 0.6/1 kV
Overall diameter 19.7 mm, about 890 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 12.6 | |
| Inner covering / bedding | Halogen-free (LSZH) | 0.80 | 14.2 |
| Wire armour | Steel | 37 × 1.25 | 16.7 |
| Sheath | Halogen-free (LSZH) | 1.5 | 19.7 |
6942B on a drum
The smallest drum that passes every check, for 19.7 mm and about 890 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 9 | 516–523 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 12 | 1,034–1,055 kg |
Barrel at least 15 × OD = 296 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: 6942B
6942B belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with 6942B
Related cables
More BS 6004 / BS 6500 / BS 7211 type numbers (UK) designations