6945X
6945X is a BS 6004 / BS 6500 / BS 7211 type numbers (UK) cable designation: 694 = Steel wire armoured (SWA) power cable, 600/1000 V; 5 = Number of cores: 5; X = XLPE insulation, PVC bedding and PVC sheath (BS 5467); 6945X = 6945X: 5 core XLPE insulated, PVC bedded, steel wire armoured, PVC sheathed power cable (Cu/XLPE/PVC/SWA/PVC, BS 5467). 600/1000 V, 90 C maximum conductor temperature (BS 5467 cl. 1). BS 5467 Table 13 (5 core, stranded copper).
1 coding system recognises this code
BS 6004 / BS 6500 / BS 7211 type numbers (UK)
| Symbol | Meaning |
|---|---|
694 | Steel wire armoured (SWA) power cable, 600/1000 V |
5 | Number of cores: 5 |
X | XLPE insulation, PVC bedding and PVC sheath (BS 5467) |
6945X | 6945X: 5 core XLPE insulated, PVC bedded, steel wire armoured, PVC sheathed power cable (Cu/XLPE/PVC/SWA/PVC, BS 5467). 600/1000 V, 90 C maximum conductor temperature (BS 5467 cl. 1). BS 5467 Table 13 (5 core, stranded copper) |
Fire behaviour (EU CPR)
PVC sheath (X).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
6945X as the cable designer builds it, 5x16 0.6/1 kV
Overall diameter 25.6 mm, about 1,710 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 17.0 | |
| Inner covering / bedding | PVC | 1.0 | 19.0 |
| Wire armour | Steel | 38 × 1.60 | 22.2 |
| Sheath | PVC | 1.7 | 25.6 |
6945X on a drum
The smallest drum that passes every check, for 25.6 mm and about 1,710 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 9 | 999–1,020 kg |
| 1,000 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 10 of 13 | 1,986–2,019 kg |
Barrel at least 15 × OD = 384 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: 6945X
6945X belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables
Terms on this page: bedding
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with 6945X
Related cables
More BS 6004 / BS 6500 / BS 7211 type numbers (UK) designations