Hazardous areas (Ex, IEC 60079-14)

Cables in explosive atmospheres suit the glands and limit flame and gas paths.

Open in the designer with this requirement

Constructions that meet it

  • Extruded inner covering (bedding): changes the cable's layers. Extruded inner covering (bedding) and compact round build with non-hygroscopic fillers (extruded PVC / LSZH). Drawbacks: Needed for compound-sealed or barrier glands.
  • Galvanised steel wire armour: changes the cable's layers. Armour (SWA or braid) for EPL Gb wiring (steel).

Writing a tender? Pro writes this requirement into your specification, ready to copy. Open in the designer with this requirement · See Pro

Tests

  • IEC 60079-14 (6th edition 2024: system-based cable selection): cable selection rules; older edition: compact circular cable, extruded bedding, non-hygroscopic fillers. Pass: flame propagation at least IEC 60332-1-2 (bunched IEC 60332-3 advised by Prysmian)

How specifications state it

'Suitable for Zone 1 / 2 acc. to IEC 60079-14': round, filled, extruded bedding, armour, flame retardant.

Where it is asked for

  • oil and gas
  • chemical plants
  • mining
  • grain and dust plants