YAKYXS
YAKYXS is een kabelaanduiding volgens PN (Poland): Y = PVC sheath; the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); y = Extruded filler / inner covering between the cores (lower-case y right after K); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; YAKYXS = YAKyXS: aluminium power cable with an extruded filler, XLPE insulation and PVC sheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
1 coderingssysteem herkent deze aanduiding
PN (Poland)
| Symbool | Betekenis |
|---|---|
Y | PVC sheath; the sheath letter comes first in Polish names |
A | Aluminium conductor (no letter: copper) |
K | kabel: power cable family (not a copper letter) |
y | Extruded filler / inner covering between the cores (lower-case y right after K) |
XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y |
YAKYXS | YAKyXS: aluminium power cable with an extruded filler, XLPE insulation and PVC sheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1 |
Brandgedrag (EU-bouwproductenverordening, CPR)
PVC-mantel (Y, YAKYXS).
Typisch nagestreefd, zoals fabrikanten dat voor dit soort constructie hebben gedeclareerd in de voorbeelden die deze site heeft gecontroleerd (niet de klasse van deze kabel):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Weergegeven als bronnen, alfabetisch per fabrikant. Geen enkele fabrikant betaalt om hier te staan.
Een CPR-klasse wordt door de fabrikant gedeclareerd in zijn prestatieverklaring en op de mantel afgedrukt (EN 50575 art. 7). Deze decoder kent geen klasse toe. Wat de CPR-klassen betekenen →
Bronnen: ontwerp EN 13501-6 en eindontwerp FprEN 50575:2014 (ontwerpen, niet de gepubliceerde teksten); IEC 60332-3-24:2000+A1:2008; ontwerp EN 13501-3 A2.