URD dimensions

Nominal calculation, not one manufacturer's datasheet. The conductor is compact aluminium as Southwire prints it; the walls are the ICEA nominals as Okonite and Southwire reproduce them, the neutral's wires are Prysmian's, and the insulation screen and the jacket are fitted to four makers' diameters, because UL 1072 and ICEA S-94-649 were not read. Check the datasheet before you specify or order.

Each row is one URD size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What URD means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 18 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
1/0 AWG15 kV 100 %4.4526.5820
2/0 AWG15 kV 100 %4.4527.5950
4/0 AWG15 kV 100 %4.4530.91,350
500 kcmil15 kV 100 %4.4537.31,800
750 kcmil15 kV 100 %4.4544.62,640
1000 kcmil15 kV 100 %4.4551.03,370
1/0 AWG15 kV 133 %5.5928.8900
2/0 AWG15 kV 133 %5.5929.81,040
4/0 AWG15 kV 133 %5.5933.11,440
500 kcmil15 kV 133 %5.5939.61,920
750 kcmil15 kV 133 %5.5946.92,780
1000 kcmil15 kV 133 %5.5953.33,530
1/0 AWG25 kV 100 %6.6031.31,000
2/0 AWG25 kV 100 %6.6032.31,150
4/0 AWG25 kV 100 %6.6035.71,560
500 kcmil25 kV 100 %6.6043.22,130
750 kcmil25 kV 100 %6.6049.42,950
1000 kcmil25 kV 100 %6.6055.83,720