N2XSEY 3x120 RM/16 12/20 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, N2XSEY 3x120 RM/16 12/20 kV comes to an overall diameter of about 70.4 mm and a weight of about 6,910 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

Main dimensions

ConductorCopper 120 mm² RM, Ø 12.9 mmIEC 60228 class 2 compacted, middle of min / max
InsulationXLPE 5.5 mmIEC 60502-2:2014 Tables 5-7, nominal insulation thickness
Diameter over insulation25.1 mm
Core diameter28.3 mm
Overall diameter70.4 mm
Weight (approximate)6,910 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1Conductor screen (semicon)Semiconducting0.614.1 (on each core)TKF at least 0.5 mm, Nexans under 1 mmtypical value, no rule
2InsulationXLPE5.525.1 (on each core)IEC 60502-2:2014 Tables 5-7, nominal insulation thicknessread in the standard
3Insulation screen (semicon)Semiconducting0.826.7 (on each core)TKF 0.8 mm, Nexans about 1 mmtypical value, no rule
4Wire screenCopper42 wires of 0.70 mm, 16 mm²28.3 (on each core)copper wire screen: wires at least 0.5 mm, 0.1 mm counter-helix tapetypical value, no rule
5FillerPPfills the space between the cores61.0
6Inner covering / beddingPVC1.664.2IEC 60502 Table 8, extruded inner covering by the fictitious diameter over the laid-up cores (Annex A)read in the standard
7SheathPVC3.170.4IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Sources and page numbers: research/mv-dimensions in the site repository.

Weight, by part

Conductors3,330 kg/km
Metal screens and armour440 kg/km
Insulation, semicon, tapes, fillers and sheaths3,140 kg/km
Total6,910 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

N2XSEY

Other sections