N2XSEH dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of N2XSEH, sized by the IEC rules the designer uses. Open a row for every layer and its source. What N2XSEH means, letter by letter.

Medium voltage, three core · 12 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
3x3512/20 kV5.557.03,670
3x5012/20 kV5.559.54,260
3x7012/20 kV5.563.25,070
3x9512/20 kV5.567.26,040
3x12012/20 kV5.570.46,960
3x15012/20 kV5.574.18,360
3x18512/20 kV5.578.09,620
3x24012/20 kV5.583.411,590
3x506/10 kV3.449.53,470
3x956/10 kV3.457.55,200
3x1506/10 kV3.464.17,370
3x2406/10 kV3.473.810,540