YAKXS
YAKXS je označení kabelu podle PN (Poland): Y = PVC sheath; the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; YAKXS = YAKXS: aluminium power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C (closest VDE: NA2XY-J / NA2XY-O). 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
Toto označení rozpoznává 1 kódovací systém
PN (Poland)
| Symbol | Význam |
|---|---|
Y | PVC sheath; the sheath letter comes first in Polish names |
A | Aluminium conductor (no letter: copper) |
K | kabel: power cable family (not a copper letter) |
XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y |
YAKXS | YAKXS: aluminium power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C (closest VDE: NA2XY-J / NA2XY-O). 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1 |
Chování při požáru (nařízení EU o stavebních výrobcích, CPR)
Plášť z PVC (Y, YAKXS).
Typické cílové třídy, jak je výrobci pro tento druh konstrukce deklarovali v příkladech ověřených tímto webem (nejde o třídu tohoto kabelu):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Uvedeno jako zdroje, abecedně podle výrobce. Žádný výrobce neplatí za to, aby se zde objevil.
Třídu CPR deklaruje výrobce v prohlášení o vlastnostech a tiskne ji na plášť (EN 50575, čl. 7). Tento dekodér žádnou třídu nepřiřazuje. Co znamenají třídy CPR →
Zdroje: návrh EN 13501-6 a konečný návrh FprEN 50575:2014 (návrhy, nikoli vydané texty); IEC 60332-3-24:2000+A1:2008; návrh EN 13501-3 A2.