YQW

YQW is a China (GB / JB/T / MT cable model codes) cable designation: YQ = 300/300 V Rubber Jacketed Flexible Cable; W = Oil And Open Weather Resistant.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of YQW 3x0.5 300/300 V:

  • YQW: YQ = 300/300 V Rubber Jacketed Flexible Cable; W = Oil And Open Weather Resistant
  • 3x0.5 300/300 V: 3 cores, each copper 0.5 mm²; rated voltage 0.3/0.3 kV

China (GB / JB/T / MT cable model codes)

SymbolMeaning
YQ300/300 V Rubber Jacketed Flexible Cable
WOil And Open Weather Resistant

How to read a China (GB / JB/T / MT cable model codes) cable code

How to read a China (GB / JB/T / MT cable model codes) cable code

A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.

What does YQ mean in a China (GB / JB/T / MT cable model codes) cable code? YQ means 300/300 V Rubber Jacketed Flexible Cable.

What does W mean in a China (GB / JB/T / MT cable model codes) cable code? W means Oil And Open Weather Resistant.

YQW as the cable designer builds it, 3x0.5 300/300 V

Overall diameter 5.5 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationEI 4 rubber0.501.9
FillerEM 2 polychloroprene4.1
SheathEM 2 polychloroprene0.705.5

YQW on a drum

The smallest drum that passes every check, for 5.5 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 3 (390 mm flange), plastic KTG drums (Europe), KTG13 of 1622 kg
1,000 mKTG 4 (435 mm flange), plastic KTG drums (Europe), KTG20 of 2042 kg

Barrel at least 12 × OD = 66 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: YQW