YJV72

YJV72 is a China (GB / JB/T / MT cable model codes) cable designation: YJ = Cross-Linked Polyethylene (XLPE); V = Polyvinyl Chloride (PVC); 7 = Non-Magnetic Metal Wire Armour; 2 = PVC (Polyvinyl Chloride) Outer Sheath.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of YJV72 4x16 0.6/1 kV:

  • YJV72: YJ = Cross-Linked Polyethylene (XLPE); V = Polyvinyl Chloride (PVC); 7 = Non-Magnetic Metal Wire Armour; 2 = PVC (Polyvinyl Chloride) Outer Sheath
  • 4x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: YJV22 · YJV62 · YJV42 · YJV32

China (GB / JB/T / MT cable model codes)

SymbolMeaning
YJCross-Linked Polyethylene (XLPE)
VPolyvinyl Chloride (PVC)
7Non-Magnetic Metal Wire Armour
2PVC (Polyvinyl Chloride) Outer Sheath

How to read a China (GB / JB/T / MT cable model codes) cable code

How to read a China (GB / JB/T / MT cable model codes) cable code

A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.

What does YJ mean in a China (GB / JB/T / MT cable model codes) cable code? YJ means Cross-Linked Polyethylene (XLPE).

What does V mean in a China (GB / JB/T / MT cable model codes) cable code? V means Polyvinyl Chloride (PVC).

What does 7 mean in a China (GB / JB/T / MT cable model codes) cable code? 7 means Non-Magnetic Metal Wire Armour.

What does 2 mean in a China (GB / JB/T / MT cable model codes) cable code? 2 means PVC (Polyvinyl Chloride) Outer Sheath; or Double Steel Tape Armour; or Radial Stainless Steel Tape Reinforcement (Oil-Filled Cables).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

YJV72: equivalents in other countries

Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)N2XYRY 4x16 RM 0,6/1 kVClosethis cable as built misses 1 of its rules
South AfricaSANS 1507-4no letters for this buildCloseInner covering / bedding 1 → 1.2 mm; Sheath 1.2 → 1.7 mm; Wire armour wire diameter 1.6 → 1.25 mm; Sheath material: not in the equivalent
United KingdomBS 5467Cu/XLPE/PVC/SWA/PVC 4x16 0,6/1 kV (to BS 5467)Closebuilt the British way: the armour on an extruded bedding, no separation sheath; Inner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm; Wire armour wire diameter 1.6 → 1.25 mm
IndiaIS 7098 (Part 1)2XWY 4x16 1100 VCloserated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm

No equivalent in: BS 6724 (asks another sheath compound); BS 7846 (asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

YJV72 as the cable designer builds it, 4x16 0.6/1 kV

Overall diameter 26.4 mm, about 1,680 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP15.2
Inner covering / beddingPVC1.017.2
SheathPVC1.219.6
Wire armourSteel40 × 1.6022.8
SheathPVC1.826.4

YJV72 on a drum

The smallest drum that passes every check, for 26.4 mm and about 1,680 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 10984–1,005 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG11 of 141,956–1,989 kg

Barrel at least 15 × OD = 396 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: YJV72

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 96 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.6 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

YJV72 belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables

Terms on this page: oversheath (outer sheath)

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro