YJLW03-Z
YJLW03-Z is a China (GB / JB/T / MT cable model codes) cable designation: YJ = Cross-Linked Polyethylene (XLPE); LW = Aluminium Sheath, Pressed Or Welded, Corrugated; 0 = No Armour; 3 = Pe (Polyethylene) Outersheath; -Z = Longitudinally Water-Blocked.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60840:2020+AMD1:2023: Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) - Test methods and requirements; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of YJLW03-Z 1x630 64/110 kV:
YJLW03-Z: YJ = Cross-Linked Polyethylene (XLPE); LW = Aluminium Sheath, Pressed Or Welded, Corrugated; 0 = No Armour; 3 = Pe (Polyethylene) Outersheath; -Z = Longitudinally Water-Blocked1x630 64/110 kV: one core, copper 630 mm²; rated voltage 64/110 kV
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
YJ | Cross-Linked Polyethylene (XLPE) |
LW | Aluminium Sheath, Pressed Or Welded, Corrugated |
0 | No Armour |
3 | Pe (Polyethylene) Outersheath |
-Z | Longitudinally Water-Blocked |
How to read a China (GB / JB/T / MT cable model codes) cable code
How to read a China (GB / JB/T / MT cable model codes) cable code
A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.
What does YJ mean in a China (GB / JB/T / MT cable model codes) cable code? YJ means Cross-Linked Polyethylene (XLPE).
What does LW mean in a China (GB / JB/T / MT cable model codes) cable code? LW means Aluminium Sheath, Pressed Or Welded, Corrugated.
What does 0 mean in a China (GB / JB/T / MT cable model codes) cable code? 0 means No Armour; or No Outersheath.
What does 3 mean in a China (GB / JB/T / MT cable model codes) cable code? 3 means Thin Steel Wire; or Pe (Polyethylene) Outersheath; or Radial And Longitudinal Copper Tape Reinforcement (Oil-Filled Cables).
What does -Z mean in a China (GB / JB/T / MT cable model codes) cable code? -Z means Longitudinally Water-Blocked.
Fire behaviour (EU CPR)
PE sheath (3).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
YJLW03-Z as the cable designer builds it, 1x630 64/110 kV
Overall diameter 89.2 mm, about 11,420 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 1.2 | 33.0 |
| Insulation | XLPE | 16.0 | 65.0 |
| Insulation screen (semicon) | Semiconducting | 1.0 | 67.0 |
| Swelling tape (water block) | Swelling | 0.50 | 68.0 |
| Corrugated metal sheath (welded) | Aluminium | 6.1 | 80.2 |
| Sheath | PE | 4.5 | 89.2 |
YJLW03-Z on a drum
The smallest drum that passes every check, for 89.2 mm and about 11,420 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 94 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
| 1,000 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
Barrel at least 25 × OD = 2,230 mm for a cable of this kind (High voltage (above 36 kV)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: YJLW03-Z
YJLW03-Z belongs to the family High voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: High voltage cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with YJLW03-Z
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.