VDE

VDE is a NBN (Belgian national cable names, ...B types) cable designation: V = Polyvinyl Chloride (PVC); D = Fine-Wired, For Welding Cables; E = Ultra Fine-Wired, For Welding Cables.

3 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of VDE 3x95 0.6/1 kV:

  • VDE: V = Polyvinyl Chloride (PVC); D = Fine-Wired, For Welding Cables; E = Ultra Fine-Wired, For Welding Cables
  • 3x95 0.6/1 kV: 3 cores, each copper 95 mm²; rated voltage 0.6/1 kV

NBN (Belgian national cable names, ...B types)

SymbolMeaning
VPolyvinyl Chloride (PVC)
DFine-Wired, For Welding Cables
EUltra Fine-Wired, For Welding Cables

How to read a NBN (Belgian national cable names, ...B types) cable code

UNE (Spain: UNE 21123 / UNE 20434)

SymbolMeaning
VPolyvinyl Chloride (PVC)
DEthylene-Propylene Rubber (EPR)
EPolyethylene (PE)

How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code

NEN 3207 / KEMA (Netherlands)

SymbolMeaning
VPolyvinyl Chloride (PVC)
DInstallation Wire (*D: Insulation Letter In Front, e.g. VD)
EPolyethylene (PE)

How to read a NEN 3207 / KEMA (Netherlands) cable code

How to read a NBN (Belgian national cable names, ...B types) cable code

A NBN (Belgian national cable names, ...B types) designation (Belgium) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 58 symbols for this system.

What does V mean in a NBN (Belgian national cable names, ...B types) cable code? V means Polyvinyl Chloride (PVC).

What does D mean in a NBN (Belgian national cable names, ...B types) cable code? D means Fine-Wired, For Welding Cables; or Sleeve (Huls, Douille).

What does E mean in a NBN (Belgian national cable names, ...B types) cable code? E means Energy Cable; or Ultra Fine-Wired, For Welding Cables; or Swelling Tape, Longitudinally Watertight (After C: Al/PE Water Barrier, Transversely Watertight).

VDE as the cable designer builds it, 3x95 0.6/1 kV

Overall diameter 38.3 mm, about 3,460 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.614.7
FillerPP31.7
Inner covering / beddingPVC1.234.1
SheathPE2.138.3

VDE on a drum

The smallest drum that passes every check, for 38.3 mm and about 3,460 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 92,006–2,039 kg
1,000 mKTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 93,939–4,060 kg

Barrel at least 15 × OD = 574 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: VDE

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 223 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 2.3 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

VDE belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables