TSLI

TSLI is a Norsk typebetegnelse (Norway) cable designation: T = 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen'); HD 620 10-K Table 4: XLPE insulation; S = 2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken; HD 620 10-K Table 4: copper screen; L = 3rd letter: aluminium laminate ('Aluminiumlaminat'); HD 620 10-K Table 4: aluminium sheath; I = 4th letter, outer sheath: halogen-free flame retardant (HD 620 10-K Table 4); TSLI = TSLI: single-core medium-voltage cable, XLPE insulation, copper wire screen, aluminium laminate, halogen-free flame retardant sheath (an A after the section: aluminium conductor). 12 kV (Um) in the Table 4 example; HD 620 10-K covers Um 12, 24 and 36 kV. HD 620 S3:2023 Part 10 Section K, Table 4 'Code designation (provisional)', p. 10-K-22 (owner's copy): T XLPE insulation, S copper screen, P PVC sheath, E PE sheath, L aluminium sheath, I halogen-free flame retardant sheath, A after the section aluminium conductor (no letter: copper); letter positions as tabled in the Nexans Kabelboka.

2 coding systems recognise this code

Norsk typebetegnelse (Norway)

SymbolMeaning
T1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen'); HD 620 10-K Table 4: XLPE insulation
S2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken; HD 620 10-K Table 4: copper screen
L3rd letter: aluminium laminate ('Aluminiumlaminat'); HD 620 10-K Table 4: aluminium sheath
I4th letter, outer sheath: halogen-free flame retardant (HD 620 10-K Table 4)
TSLITSLI: single-core medium-voltage cable, XLPE insulation, copper wire screen, aluminium laminate, halogen-free flame retardant sheath (an A after the section: aluminium conductor). 12 kV (Um) in the Table 4 example; HD 620 10-K covers Um 12, 24 and 36 kV. HD 620 S3:2023 Part 10 Section K, Table 4 'Code designation (provisional)', p. 10-K-22 (owner's copy): T XLPE insulation, S copper screen, P PVC sheath, E PE sheath, L aluminium sheath, I halogen-free flame retardant sheath, A after the section aluminium conductor (no letter: copper); letter positions as tabled in the Nexans Kabelboka

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
TCross-Linked Polyethylene (XLPE)
SBedding Or Taping + Concentric Conductor
LAluminium (Laminated To Outer Jacket)
IThermoplastic Compound, Halogen-Free (Nexans Norway key: other plastics, e.g. TPE)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

Fire behaviour (EU CPR)

  • Halogen-free compound (I). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

  • Flame retardant (I). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

TSLI: equivalents in other countries

Shown for 1x240/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502Al/XLPE/CWS/LSZH 1x240/25 12/20 kV (to IEC 60502-2)EquivalentSheath 2.2 → 2.1 mm; Overall diameter 39.8 → 39.6 mm
NetherlandsHD 620 S3 10-Jno letters for this buildCloseSheath 2.2 → 2.5 mm; Overall diameter 39.8 → 40.4 mm; this cable as built misses 1 of its rules
GermanyHD 620 S3 10-C (DIN VDE 0276-620)NA2XS(FL)H 1x240 RM/25 12/20 kVCloseInsulation screen (semicon) 0.8 → 0.6 mm; Sheath 2.2 → 2.5 mm; Overall diameter 39.8 → 40 mm; this cable as built misses 2 of its rules
SwedenHD 620 S3 10-MAXCQJ-TT 1x240/35 12/20 (24) kV (NKT writes a near build without the C (AXLJ))Closescreen 25 → 35 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 39.8 → 39.4 mm; this cable as built misses 2 of its rules
DenmarkHD 620 S3 10-Dno letters for this buildClosescreen 25 → 35 mm² (HD 620 10-D Table 1); Sheath 2.2 → 3 mm; Overall diameter 39.8 → 41.4 mm; this cable as built misses 2 of its rules

No equivalent in: BS 6622 (armoured cables only).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

TSLI as the cable designer builds it, 1x240/25 12/20 kV

Overall diameter 39.8 mm, about 1,900 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6019.6
InsulationXLPE5.530.6
Insulation screen (semicon)Semiconducting0.8032.2
Swelling tape (water block)Swelling0.3032.8
Wire screenCopper65 × 0.7034.4
Swelling tape (water block)Swelling0.3035.0
Laminate (radial water block)Aluminium0.2035.4
SheathHalogen-free (LSZH)2.239.8

TSLI on a drum

The smallest drum that passes every check, for 39.8 mm and about 1,900 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG7 of 81,291–1,363 kg
1,000 mKTG 22 (2200 to 2240 mm flange), wood KTG drums (Europe), Bayka, KTG7 of 82,460–2,653 kg

Barrel at least 25 × OD = 995 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: TSLI

TSLI belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Terms on this page: bedding · oversheath (outer sheath)