THW-LS
THW-LS is a NOM / NMX (Mexico) cable designation: T = Thermoplastic (Termoplastico) insulation; W = Resistant to water (Resistente al agua); LS = Low smoke emission (Baja emision de humos); PVC-LS is flame-retardant, low smoke, low HCl, not halogen-free; THW-LS = Thermoplastic water-resistant low-smoke building wire (Mexico). 600 V, 90 C dry, 75 C wet. NOM-063-SCFI; NMX-J-010-ANCE.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: UL 83 (edition 16): Thermoplastic-Insulated Wires and Cables. How the values are sourced
Worked reading of THW-LS 12 AWG, 600 V:
THW-LS: T = Thermoplastic (Termoplastico) insulation; W = Resistant to water (Resistente al agua); LS = Low smoke emission (Baja emision de humos); PVC-LS is flame-retardant, low smoke, low HCl, not halogen-free; THW-LS = Thermoplastic water-resistant low-smoke building wire (Mexico). 600 V, 90 C dry, 75 C wet. NOM-063-SCFI; NMX-J-010-ANCE12 AWG, 600 V: one core, copper 12 AWG (3.3 mm²); rated voltage 600 V
NOM / NMX (Mexico)
| Symbol | Meaning |
|---|---|
T | Thermoplastic (Termoplastico) insulation |
W | Resistant to water (Resistente al agua) |
LS | Low smoke emission (Baja emision de humos); PVC-LS is flame-retardant, low smoke, low HCl, not halogen-free |
THW-LS | Thermoplastic water-resistant low-smoke building wire (Mexico). 600 V, 90 C dry, 75 C wet. NOM-063-SCFI; NMX-J-010-ANCE |
What is THW-LS cable?
THW-LS: Thermoplastic water-resistant low-smoke building wire (Mexico). Rating: 600 V, 90 C dry, 75 C wet. Standard: NOM-063-SCFI; NMX-J-010-ANCE.
Relsamex (Vinanel THW-LS) gives 90 C dry and 75 C wet; the 90 C wet figure on other pages belongs to THHW-LS. Vinanel XXI is Condumex's brand. Concentric soft copper. Marks CT, SR, AF, RPI in Condelmex titles are UNVERIFIED (search snippets read CT as tray-rated, SR as sunlight resistant).
Documents and pages the readings were taken from
Fire behaviour (EU CPR)
PVC sheath (LS).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
THW-LS: equivalents in other countries
Shown for 1x3.31 600 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | no letters for this build | Close | Insulation 0.76 → 1 mm; Overall diameter 3.79 → 4.27 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
THW-LS as the cable designer builds it, 12 AWG, 600 V
Overall diameter 3.8 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.76 | 3.8 |
THW-LS on a drum
The smallest drum that passes every check, for 3.8 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 14x10x5, wood NEMA reels (North America), Okonite | 15 of 18 | 22 kg |
| 1,000 m | NEMA 18x10x6, wood NEMA reels (North America), Okonite | 23 of 29 | 45 kg |
Barrel at least 20 × OD = 76 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: THW-LS
THW-LS belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²