SCB
SCB is a Thermocouple cables (IEC 60584-3) cable designation: S = Thermocouple type S: Cu / CuNi (positive / negative leg); CB = CB: compensating cable (C) with a substitute alloy, variant B; SCB = SCB: compensating cable, substitute alloy for a type S thermocouple, Cu / CuNi (substitute alloy). insulation limits by the material pair (Lapp T8): PVC -25 to +80 C, silicone -50 to +180 C, glass silk -50 to +200 C, FEP -100 to +205 C. IEC 60584-3; ANSI MC96.1 / ASTM E230 (US colour code).
1 coding system recognises this code
Thermocouple cables (IEC 60584-3)
| Symbol | Meaning |
|---|---|
S | Thermocouple type S: Cu / CuNi (positive / negative leg) |
CB | CB: compensating cable (C) with a substitute alloy, variant B |
SCB | SCB: compensating cable, substitute alloy for a type S thermocouple, Cu / CuNi (substitute alloy). insulation limits by the material pair (Lapp T8): PVC -25 to +80 C, silicone -50 to +180 C, glass silk -50 to +200 C, FEP -100 to +205 C. IEC 60584-3; ANSI MC96.1 / ASTM E230 (US colour code) |