RVFV
RVFV is a UTE (France, NF C 30-202 traditional system) cable designation: R = Cross-Linked Polyethylene (XLPE); VF = Nitril-Rubber; V = Polyvinyl Chloride (PVC).
7 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of RVFV 3x95 0.6/1 kV:
RVFV: R = Cross-Linked Polyethylene (XLPE); VF = Nitril-Rubber; V = Polyvinyl Chloride (PVC)3x95 0.6/1 kV: 3 cores, each copper 95 mm²; rated voltage 0.6/1 kV
Related cable types: RVFV-K · U-1000 RVFV · U1000-ARVFV
UTE (France, NF C 30-202 traditional system)
| Symbol | Meaning |
|---|---|
R | Cross-Linked Polyethylene (XLPE) |
VF | Nitril-Rubber |
V | Polyvinyl Chloride (PVC) |
How to read a UTE (France, NF C 30-202 traditional system) cable code
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
R | Flexible Cable |
VF | Nitrile (Butyronitrile) Rubber Sheath |
V | Polyvinyl Chloride (PVC) |
How to read a China (GB / JB/T / MT cable model codes) cable code
CEI-UNEL 35011 (Italy)
| Symbol | Meaning |
|---|---|
R | Multi-Wire, Round-Section, Class 2 |
V | Impregnated Glass Tape |
F | Round Steel Wire |
V | Impregnated Glass Tape |
Norwegian type designation (NEK 606 offshore and Norwegian land cables)
| Symbol | Meaning |
|---|---|
R | Ethylenepropylene Rubber (EPR) |
V | Screen (Draka key: aluminium screen; Nexans key: screen, optionally with PVC) |
F | Flat Steel Wire Armour |
V | Other Halogen-Free Thermoset Materials (Draka BFOV: oil-resistant HNBR; Nexans Norway key: EVA) |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
UNE (Spain: UNE 21123 / UNE 20434)
| Symbol | Meaning |
|---|---|
R | Cross-Linked Polyethylene (XLPE) |
V | Polyvinyl Chloride (PVC) |
F | Helical Galvanized Steel Tape |
V | Polyvinyl Chloride (PVC) |
NEN 3207 / KEMA (Netherlands)
| Symbol | Meaning |
|---|---|
R | Round Conductor |
V | Polyvinyl Chloride (PVC) |
F | Fine-Wired In Flexible Cables-Class 5 |
V | Polyvinyl Chloride (PVC) |
SS 424 17 01 (Sweden)
| Symbol | Meaning |
|---|---|
R | Copper Conductor, Many-Stranded, Flexible (Class 5) |
V | Rubber Without Outer Sheath (Older Cables: Natural Rubber) |
F | Copper Screen As Braid |
V | For Laying In Water |
How to read a UTE (France, NF C 30-202 traditional system) cable code
A UTE (France, NF C 30-202 traditional system) designation (France) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 30 symbols for this system.
What does R mean in a UTE (France, NF C 30-202 traditional system) cable code? R means Cross-Linked Polyethylene (XLPE).
What does VF mean in a UTE (France, NF C 30-202 traditional system) cable code? VF means Nitril-Rubber.
What does V mean in a UTE (France, NF C 30-202 traditional system) cable code? V means Polyvinyl Chloride (PVC).
Fire behaviour (EU CPR)
PVC sheath (V).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
RVFV as the cable designer builds it, 3x95 0.6/1 kV
Overall diameter 38.3 mm, about 3,580 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.6 | 14.7 |
| Filler | PP | 31.7 | |
| Inner covering / bedding | PVC | 1.2 | 34.1 |
| Sheath | PVC | 2.1 | 38.3 |
RVFV on a drum
The smallest drum that passes every check, for 38.3 mm and about 3,580 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 9 | 2,066–2,099 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 9 | 4,059–4,180 kg |
Barrel at least 15 × OD = 574 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: RVFV
RVFV belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables