RHZ1-RA-2OL
RHZ1-RA-2OL is a UNE (Spain: UNE 21123 / UNE 20434) cable designation: RH = Cross-Linked Polyethylene (XLPE); Z1 = Low Smoke Zero Halogen Compound; RA = Aluminium (Laminated To Outer Jacket); 2OL = Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60840:2020+AMD1:2023: Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) - Test methods and requirements; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of RHZ1-RA-2OL 1x630/95 64/110 kV:
RHZ1-RA-2OL: RH = Cross-Linked Polyethylene (XLPE); Z1 = Low Smoke Zero Halogen Compound; RA = Aluminium (Laminated To Outer Jacket); 2OL = Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket)1x630/95 64/110 kV: one core, copper 630 mm²; rated voltage 64/110 kV
Related cable types: RHZ1-2OL
UNE (Spain: UNE 21123 / UNE 20434)
| Symbol | Meaning |
|---|---|
RH | Cross-Linked Polyethylene (XLPE) |
Z1 | Low Smoke Zero Halogen Compound |
RA | Aluminium (Laminated To Outer Jacket) |
2OL | Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket) |
How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code
A UNE (Spain: UNE 21123 / UNE 20434) designation (Spain) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 56 symbols for this system.
What does RH mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? RH means Cross-Linked Polyethylene (XLPE).
What does Z1 mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? Z1 means Low Smoke Zero Halogen Compound.
What does RA mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? RA means Aluminium (Laminated To Outer Jacket).
What does 2OL mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? 2OL means Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket).
Fire behaviour (EU CPR)
Halogen-free compound (Z1). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
RHZ1-RA-2OL as the cable designer builds it, 1x630/95 64/110 kV
Overall diameter 79.2 mm, about 10,410 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 1.2 | 33.0 |
| Insulation | XLPE | 16.0 | 65.0 |
| Insulation screen (semicon) | Semiconducting | 1.0 | 67.0 |
| Swelling tape (water block) | Swelling | 0.50 | 68.0 |
| Wire screen | Copper | 247 × 0.70 | 69.6 |
| Swelling tape (water block) | Swelling | 0.50 | 70.6 |
| Laminate (radial water block) | Aluminium | 0.30 | 71.2 |
| Sheath | PE | 4.0 | 79.2 |
RHZ1-RA-2OL on a drum
The smallest drum that passes every check, for 79.2 mm and about 10,410 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 83 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
| 1,000 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
Barrel at least 25 × OD = 1,980 mm for a cable of this kind (High voltage (above 36 kV)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: RHZ1-RA-2OL
RHZ1-RA-2OL belongs to the family High voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: High voltage cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with RHZ1-RA-2OL
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.