PP/R

PP/R is a JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia) cable designation: P = PVC insulation; P = PVC sheath; /R = /R: flat cable, cores laid side by side in a PVC web (for plaster); PP/R = PP/R: flat PVC installation cable, the cores laid side by side in a PVC web (NYIFY, for laying in plaster). 380 V, test voltage 2 kV (Novkabel p.41). SRPS N.C3.230.

1 coding system recognises this code

JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia)

SymbolMeaning
PPVC insulation
PPVC sheath
/R/R: flat cable, cores laid side by side in a PVC web (for plaster)
PP/RPP/R: flat PVC installation cable, the cores laid side by side in a PVC web (NYIFY, for laying in plaster). 380 V, test voltage 2 kV (Novkabel p.41). SRPS N.C3.230

What is PP/R cable?

PP/R: flat PVC installation cable, the cores laid side by side in a PVC web (NYIFY, for laying in plaster). Rating: 380 V, test voltage 2 kV (Novkabel p.41). Standard: SRPS N.C3.230.

Novkabel pdf p.41: 'PVC compound layer over 2 or 3 cores, which are laid parallel', grey or black, sizes 2x1,5 to 3x2,5. Kabeltrade: 'NIYFY-J: PP/R, YDY'; Blue Line: 'Kabl PP/R (NYIFY)'. Kabeltrade comparison table and elteh.net 'Stare i nove oznake kabela' print the same pairs.

Documents and pages the readings were taken from

JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

PP/R: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NYY 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules
IndiaIS 1554 (Part 1)YY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

PP/R as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.7 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
SheathPVC1.49.7

PP/R on a drum

The smallest drum that passes every check, for 9.7 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 14117 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16251–255 kg

Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: PP/R

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 4.2 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

PP/R belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables