PFXP
PFXP is a Norsk typebetegnelse (Norway) cable designation: P = 1st letter, insulation: PVC ('P=Polyvinylklorid - PVC'); F = 2nd letter, bedding or filler sheath ('F=Fyllkappe'; Kabelboka: 'Fyllkappe/ båndering'); X = 3rd letter: no armour or screen ('X=Ingen armering/skjerm'; Kabelboka: 'Ingen armering e.l.'); P = 4th letter, outer sheath: PVC ('P=PVC-ytterkappe'); PFXP = PFXP: PVC-insulated, filler-sheathed, unarmoured, PVC-sheathed installation cable with stranded copper cores, 300/500 V. 300/500 V, 70 C conductor (Nexans). NEK 535 (Nexans Norway PFXP 300/500 V).
2 coding systems recognise this code
Norsk typebetegnelse (Norway)
| Symbol | Meaning |
|---|---|
P | 1st letter, insulation: PVC ('P=Polyvinylklorid - PVC') |
F | 2nd letter, bedding or filler sheath ('F=Fyllkappe'; Kabelboka: 'Fyllkappe/ båndering') |
X | 3rd letter: no armour or screen ('X=Ingen armering/skjerm'; Kabelboka: 'Ingen armering e.l.') |
P | 4th letter, outer sheath: PVC ('P=PVC-ytterkappe') |
PFXP | PFXP: PVC-insulated, filler-sheathed, unarmoured, PVC-sheathed installation cable with stranded copper cores, 300/500 V. 300/500 V, 70 C conductor (Nexans). NEK 535 (Nexans Norway PFXP 300/500 V) |
Norwegian type designation (NEK 606 offshore and Norwegian land cables)
| Symbol | Meaning |
|---|---|
P | Polyvinylchloride (PVC) |
F | Bedding Or Taping (Halogen-Free) |
X | No Armour |
P | Polyvinyl Chloride (PVC) |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
What is PFXP cable?
PFXP: PVC-insulated, filler-sheathed, unarmoured, PVC-sheathed installation cable with stranded copper cores, 300/500 V. Rating: 300/500 V, 70 C conductor (Nexans). Standard: NEK 535 (Nexans Norway PFXP 300/500 V).
Nexans Norway (manufacturer): 'PFXP 300/500 V Installation cable with copper conductor', double-insulated, annealed copper, round stranded (7 strands), PVC insulation, PVC filler / inner sheath, white PVC outer sheath, NEK 535, IEC 60332-1-2, 70 C; nominal outer diameters 3G1.5 9.1, 4G1.5 9.8, 5G1.5 10.6, 3G2.5 10.5, 5G2.5 12.4, 3G4 12.0, 5G6 15.6 mm. NEK Kabel 'Typebetegnelser og firebokstavkoden' (modified 5 April 2019, p. 9): 1st letter P 'Polyvinylklorid - PVC' (insulation), 2nd F 'Fyllkappe / baandering', 3rd X 'Ingen armering e.l.', 4th P 'Polyvinylklorid - PVC' (outer sheath). PFXP is a PVC cable, not a halogen-free one: Nexans names PVC for the insulation, the filler and the sheath. No maker read prints the wall thicknesses.
Documents and pages the readings were taken from
Norsk typebetegnelse (Norway): how to read the cable type names
Fire behaviour (EU CPR)
PVC sheath (P).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Laying, sizes and datasheet: PFXP
Terms on this page: bedding · oversheath (outer sheath)