NHXMH

NHXMH is a DIN VDE type names (Germany) cable designation: N = German national (VDE) type; HX = Crosslinked polyethylene insulation 2XI1 (DIN VDE 0276-604), halogen-free: 0,5 mm at 1,5 and 2,5 mm², 0,6 at 4 and 6, 0,7 at 10 and 16, 0,9 at 25 and 35 mm² (DIN VDE 0250-214 Table 1); MH = Sheath of the halogen-free thermoplastic HM2 (Annex A, 70 °C), 1,4 to 1,8 mm, over a halogen-free common covering, 0,4 to 1,4 mm (it may be left off a single core) (DIN VDE 0250-214 5.6, 5.7, Table 1); NHXMH = NHXMH: halogen-free installation cable with improved behaviour in a fire, the type of DIN VDE 0250-214. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-214:2002-04 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1, e.g. 3 x 1,5 mm²: 8,0 to 9,6 mm; tests, Table 2: 2 kV a.c. for 5 min, flame DIN EN 50266-2-4, corrosivity DIN EN 50267-2-2, smoke density DIN EN 50268-2).

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NHXMH 4x1.5 300/500 V:

  • NHXMH: N = German national (VDE) type; HX = Crosslinked polyethylene insulation 2XI1 (DIN VDE 0276-604), halogen-free: 0,5 mm at 1,5 and 2,5 mm², 0,6 at 4 and 6, 0,7 at 10 and 16, 0,9 at 25 and 35 mm² (DIN VDE 0250-214 Table 1); MH = Sheath of the halogen-free thermoplastic HM2 (Annex A, 70 °C), 1,4 to 1,8 mm, over a halogen-free common covering, 0,4 to 1,4 mm (it may be left off a single core) (DIN VDE 0250-214 5.6, 5.7, Table 1); NHXMH = NHXMH: halogen-free installation cable with improved behaviour in a fire, the type of DIN VDE 0250-214. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-214:2002-04 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1, e.g. 3 x 1,5 mm²: 8,0 to 9,6 mm; tests, Table 2: 2 kV a.c. for 5 min, flame DIN EN 50266-2-4, corrosivity DIN EN 50267-2-2, smoke density DIN EN 50268-2)
  • 4x1.5 300/500 V: 4 cores, each copper 1.5 mm²; rated voltage 0.3/0.5 kV

Related cable types: NHXMH-J · NHXMH/Q · NHXMH FE180 · 3x2,5 NHXMH

DIN VDE type names (Germany)

SymbolMeaning
NGerman national (VDE) type
HXCrosslinked polyethylene insulation 2XI1 (DIN VDE 0276-604), halogen-free: 0,5 mm at 1,5 and 2,5 mm², 0,6 at 4 and 6, 0,7 at 10 and 16, 0,9 at 25 and 35 mm² (DIN VDE 0250-214 Table 1)
MHSheath of the halogen-free thermoplastic HM2 (Annex A, 70 °C), 1,4 to 1,8 mm, over a halogen-free common covering, 0,4 to 1,4 mm (it may be left off a single core) (DIN VDE 0250-214 5.6, 5.7, Table 1)
NHXMHNHXMH: halogen-free installation cable with improved behaviour in a fire, the type of DIN VDE 0250-214. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-214:2002-04 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1, e.g. 3 x 1,5 mm²: 8,0 to 9,6 mm; tests, Table 2: 2 kV a.c. for 5 min, flame DIN EN 50266-2-4, corrosivity DIN EN 50267-2-2, smoke density DIN EN 50268-2)

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
HXCross-Linked Halogen-Free Polymer Compound
MHConnecting Cable, Moderate Mechanical Load

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

What is NHXMH cable?

NHXMH: halogen-free installation cable with improved behaviour in a fire, the type of DIN VDE 0250-214. Rating: U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). Standard: DIN VDE 0250-214:2002-04 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1, e.g. 3 x 1,5 mm²: 8,0 to 9,6 mm; tests, Table 2: 2 kV a.c. for 5 min, flame DIN EN 50266-2-4, corrosivity DIN EN 50267-2-2, smoke density DIN EN 50268-2).

NHXMH-J has a green-and-yellow core, NHXMH-O none (3.2). The letter reading below this row is the DIN VDE 0250 letter code; this row is the type as the standard defines it.

Documents and pages the readings were taken from

  • DIN VDE 0250-214:2002-04 (clauses 3 to 7 p. 4 to 6, Table 1 and Table 2)

DIN VDE type names (Germany): how to read the cable type names

Fire behaviour (EU CPR)

  • Halogen-free compound (HX, MH, NHXMH). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NHXMH: equivalents in other countries

Shown for 4x1.5 300/500 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
ChinaGB/T 9330WDZ-KYJY 4x1.5 450/750 VCloserated higher: 450/750 V (this cable 300/500 V); Insulation 0.5 → 0.6 mm; Inner covering / bedding material: not in the equivalent; Sheath 1.4 → 1.2 mm

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

NHXMH as the cable designer builds it, 4x1.5 300/500 V

Overall diameter 9.4 mm, about 140 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.502.4
FillerHalogen-free (LSZH)5.8
Inner covering / beddingHalogen-free (LSZH)0.406.6
SheathHalogen-free (LSZH)1.49.4

NHXMH on a drum

The smallest drum that passes every check, for 9.4 mm and about 140 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1477 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 17171–175 kg

Barrel at least 15 × OD = 140 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NHXMH

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NHXMH

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More DIN VDE type names (Germany) designations

NHXMH