MP-GC is a NEC / UL (USA) cable designation: MP = Mine power feeder cable for permanent installation (Prysmian: Mine Power Feeder); GC = Ground-check conductor, yellow polypropylene insulated, for fail-safe ground monitoring; MP-GC = MP-GC: mine power feeder cable with ground check, three shielded EPR (or XLP) cores with copper tape shields, two grounding conductors and a ground-check conductor, CPE (or PVC) jacket, 5 to 35 kV, for permanent installation. 5000 V to 35000 V, 90 C, 100 % insulation level (Prysmian, Tele-Fonika). ICEA S-75-381 / NEMA WC 58; MSHA.

2 coding systems recognise this code

NEC / UL (USA)

SymbolMeaning
MPMine power feeder cable for permanent installation (Prysmian: Mine Power Feeder)
GCGround-check conductor, yellow polypropylene insulated, for fail-safe ground monitoring
MP-GCMP-GC: mine power feeder cable with ground check, three shielded EPR (or XLP) cores with copper tape shields, two grounding conductors and a ground-check conductor, CPE (or PVC) jacket, 5 to 35 kV, for permanent installation. 5000 V to 35000 V, 90 C, 100 % insulation level (Prysmian, Tele-Fonika). ICEA S-75-381 / NEMA WC 58; MSHA

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
MExpanded PE Or PP + Filling Compound
PPolyvinyl Chloride (PVC)
GPE + PA (Nexans Norway key: natural rubber)
CPolychloroprene (Neoprene, PCP) or Chlorinated Polyethylene (CPE) (Nexans Norway key: improved hydrocarbon resistance)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

What is MP-GC cable?

MP-GC: mine power feeder cable with ground check, three shielded EPR (or XLP) cores with copper tape shields, two grounding conductors and a ground-check conductor, CPE (or PVC) jacket, 5 to 35 kV, for permanent installation. Rating: 5000 V to 35000 V, 90 C, 100 % insulation level (Prysmian, Tele-Fonika). Standard: ICEA S-75-381 / NEMA WC 58; MSHA.

Prysmian NA mining catalogue p.24-32 'Type MP-GC EPR/CPE, Mine Power Feeder w/ Ground Check' 8000 to 35000 V and 'MP-GC XLP/PVC' 5000 to 35000 V: bare compact class B copper, extruded strand shield, EPR, extruded insulation shield with black, white and red marker strips, overlapped copper tape shield, yellow polypropylene ground-check conductor, two bare grounding conductors, CPE jacket, 'Provides high-voltage distribution intended for permanent installations'. Tele-Fonika 'MP-GC 8000V/15000V EPR/CPE ... Mine power feeder', ICEA S-75-381/NEMA WC-58.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

Laying, sizes and datasheet: MP-GC

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Work with MP-GC

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations

MP-GC