FS17
FS17 is a CEI-UNEL 35011 (Italy) cable designation: F = Fine-Wired In Flexible Cables-Class 5; S17 = PVC Insulation (S17).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of FS17 1x1.5 450/750 V:
FS17: F = Fine-Wired In Flexible Cables-Class 5; S17 = PVC Insulation (S17)1x1.5 450/750 V: one core, copper 1.5 mm²; rated voltage 0.45/0.75 kV
CEI-UNEL 35011 (Italy)
| Symbol | Meaning |
|---|---|
F | Fine-Wired In Flexible Cables-Class 5 |
S17 | PVC Insulation (S17) |
How to read a CEI-UNEL 35011 (Italy) cable code
A CEI-UNEL 35011 (Italy) designation (Italy) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 85 symbols for this system.
What does F mean in a CEI-UNEL 35011 (Italy) cable code? F means Fine-Wired In Flexible Cables-Class 5; or Round Steel Wire.
What does S17 mean in a CEI-UNEL 35011 (Italy) cable code? S17 means PVC Insulation (S17).
FS17: equivalents in other countries
Shown for 1x1.5 450/750 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Europe | EN 50525-2-31 | H07V-K 1x1,5 450/750 V | Equivalent | every value the same |
| India | IS 694 | FR 1x1,5 1100 V | Close | rated higher: 1100 V (this cable 450/750 V); Insulation 0.7 → 0.6 mm; Overall diameter 2.95 → 2.75 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
FS17 as the cable designer builds it, 1x1.5 450/750 V
Overall diameter 2.9 mm, about 20 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.70 | 2.9 |
FS17 on a drum
The smallest drum that passes every check, for 2.9 mm and about 20 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 3 (390 mm flange), plastic KTG drums (Europe), KTG | 9 of 30 | 12 kg |
| 1,000 m | KTG 3 (390 mm flange), plastic KTG drums (Europe), KTG | 15 of 30 | 22 kg |
Barrel at least 12 × OD = 35 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: FS17
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with FS17
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.