FKKJ

FKKJ is a SS 424 17 01 (Sweden) cable designation: F = Copper Conductor, Few-Stranded (Class 2); K = Polyvinyl Chloride (PVC); K = Polyvinyl Chloride (PVC); J = Underground Use.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of FKKJ 3x95 0.6/1 kV:

  • FKKJ: F = Copper Conductor, Few-Stranded (Class 2); K = Polyvinyl Chloride (PVC); K = Polyvinyl Chloride (PVC); J = Underground Use
  • 3x95 0.6/1 kV: 3 cores, each copper 95 mm²; rated voltage 0.6/1 kV

SS 424 17 01 (Sweden)

SymbolMeaning
FCopper Conductor, Few-Stranded (Class 2)
KPolyvinyl Chloride (PVC)
KPolyvinyl Chloride (PVC)
JUnderground Use

How to read a SS 424 17 01 (Sweden) cable code

How to read a SS 424 17 01 (Sweden) cable code

A SS 424 17 01 (Sweden) designation (Sweden) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 90 symbols for this system.

What does F mean in a SS 424 17 01 (Sweden) cable code? F means Copper Conductor, Few-Stranded (Class 2); or Copper Screen As Braid; or Copper or Steel Braid; or Firmly Attached Outer Conductive Layer, Medium Voltage Cable.

What does K mean in a SS 424 17 01 (Sweden) cable code? K means Polyvinyl Chloride (PVC).

What does J mean in a SS 424 17 01 (Sweden) cable code? J means Steel Wire Conductor; or Steel Tape Armour; or Underground Use; or For Laying In Ground.

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

FKKJ: equivalents in other countries

Shown for 3x95 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NYY 3x95 RM 0,6/1 kVEquivalentevery value the same
IndiaIS 1554 (Part 1)YY 3x95 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1.2 → 0.4 mm; Sheath 2.1 → 2.2 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

FKKJ as the cable designer builds it, 3x95 0.6/1 kV

Overall diameter 38.3 mm, about 3,580 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.614.7
FillerPP31.7
Inner covering / beddingPVC1.234.1
SheathPVC2.138.3

FKKJ on a drum

The smallest drum that passes every check, for 38.3 mm and about 3,580 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 92,066–2,099 kg
1,000 mKTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 94,059–4,180 kg

Barrel at least 15 × OD = 574 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: FKKJ

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 223 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 2.3 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

FKKJ belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables