CYY-F

CYY-F is a Romania (STAS 9436 national symbols) cable designation: C = Power Cable (Low And Medium Voltage); Y = Polyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering; Y = Polyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering; -F = Flame Retardant.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of CYY-F 1x16 0.6/1 kV:

  • CYY-F: C = Power Cable (Low And Medium Voltage); Y = Polyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering; Y = Polyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering; -F = Flame Retardant
  • 1x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: CYY-FJ · CYY-F 3x1.5 · CYY-F 3x120+70 · acyyf · cyy

Romania (STAS 9436 national symbols)

SymbolMeaning
CPower Cable (Low And Medium Voltage)
YPolyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering
YPolyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering
-FFlame Retardant

How to read a Romania (STAS 9436 national symbols) cable code

CSN (Czech Republic, Slovakia)

SymbolMeaning
CCopper conductor
YPVC insulation
YAdditional PVC insulation
CYYCYY: single-core solid copper wire with a second PVC insulation layer, only for screening and signal purposes, 450/750 V. 450/750 V. PN-KT-081-09 (NKT)

How to read a Romania (STAS 9436 national symbols) cable code

A Romania (STAS 9436 national symbols) designation (Romania) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 22 symbols for this system.

What does C mean in a Romania (STAS 9436 national symbols) cable code? C means Power Cable (Low And Medium Voltage).

What does Y mean in a Romania (STAS 9436 national symbols) cable code? Y means Polyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering.

What does -F mean in a Romania (STAS 9436 national symbols) cable code? -F means Flame Retardant.

Fire behaviour (EU CPR)

  • Flame retardant (-F). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

  • PVC sheath (Y).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

CYY-F: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NYY 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules
IndiaIS 1554 (Part 1)YY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

CYY-F as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.7 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
SheathPVC1.49.7

CYY-F on a drum

The smallest drum that passes every check, for 9.7 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 14117 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16251–255 kg

Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: CYY-F

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 4.2 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

CYY-F belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with CYY-F

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More Romania (STAS 9436 national symbols) designations

CYY-F