CYKY-O

CYKY-O is a CSN (Czech Republic, Slovakia) cable designation: C = Copper conductor; Y = PVC insulation, normal type; K = kabel: a cable proper, for fixed installation; Y = PVC sheath; -O = Without a green-yellow protective core (ohne); CYKY = CYKY: copper installation cable, PVC insulation and PVC sheath, 450/750 V, 2 to 48 cores (no European equivalent per NKT; do not read it as NYM-J). 450/750 V. TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab).

1 coding system recognises this code

Standard, worked reading and related types

Worked reading of CYKY-O:

  • CYKY-O: C = Copper conductor; Y = PVC insulation, normal type; K = kabel: a cable proper, for fixed installation; Y = PVC sheath; -O = Without a green-yellow protective core (ohne); CYKY = CYKY: copper installation cable, PVC insulation and PVC sheath, 450/750 V, 2 to 48 cores (no European equivalent per NKT; do not read it as NYM-J). 450/750 V. TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab)

Related cable types: CYKY

CSN (Czech Republic, Slovakia)

SymbolMeaning
CCopper conductor
YPVC insulation, normal type
Kkabel: a cable proper, for fixed installation
YPVC sheath
-OWithout a green-yellow protective core (ohne)
CYKYCYKY: copper installation cable, PVC insulation and PVC sheath, 450/750 V, 2 to 48 cores (no European equivalent per NKT; do not read it as NYM-J). 450/750 V. TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab)

What is CYKY cable?

CYKY: copper installation cable, PVC insulation and PVC sheath, 450/750 V, 2 to 48 cores (no European equivalent per NKT; do not read it as NYM-J). Rating: 450/750 V. Standard: TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab).

Bedding under the sheath, black UV-resistant sheath. NKT states in a Slovak trademark decision that CYKY has no comparable European equivalent; NYM-J is listed separately in the NKT catalogue (VDE 0250-204). -J / -O after the name says with / without the green-yellow core; CYKY is sold -J by default. Counts: 4J1,5, 4Bx1,5 and 4-J all mean 4 cores including a green-yellow one; the B / C / D letters after a count are colour-scheme codes of the old CSN 33 0165 table, not a "without protective core" flag. 3x150+70 is three 150 mm2 cores plus one smaller 70 mm2 core (PE or PEN).

Documents and pages the readings were taken from

CSN (Czech Republic, Slovakia): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Work with CYKY-O

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More CSN (Czech Republic, Slovakia) designations

CYKY-O