CU/XLPE/PVC/SWA/ PVC

CU/XLPE/PVC/SWA/ PVC is a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable designation: CU = Copper Conductor; XLPE = Cross-Linked Polyethylene (XLPE); PVC = Polyvinyl Chloride (PVC); SWA = Steel Wire Armour (round galvanised steel wires); PVC = Polyvinyl Chloride (PVC).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of CU/XLPE/PVC/SWA/ PVC 3x16 0.6/1 kV:

  • CU/XLPE/PVC/SWA/ PVC: CU = Copper Conductor; XLPE = Cross-Linked Polyethylene (XLPE); PVC = Polyvinyl Chloride (PVC); SWA = Steel Wire Armour (round galvanised steel wires); PVC = Polyvinyl Chloride (PVC)
  • 3x16 0.6/1 kV: 3 cores, each copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: Cu-XLPE-PVC-SWA-PVC-SWA-PVC · AL/XLPE/PVC/SWA/PVC

Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice)

SymbolMeaning
CUCopper Conductor
XLPECross-Linked Polyethylene (XLPE)
PVCPolyvinyl Chloride (PVC)
SWASteel Wire Armour (round galvanised steel wires)
PVCPolyvinyl Chloride (PVC)

How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code

How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code

A Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designation (UK / International) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 119 symbols for this system.

What does CU mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? CU means Copper Conductor.

What does XLPE mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? XLPE means Cross-Linked Polyethylene (XLPE).

What does PVC mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? PVC means Polyvinyl Chloride (PVC).

What does SWA mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? SWA means Steel Wire Armour (round galvanised steel wires).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

CU/XLPE/PVC/SWA/ PVC: equivalents in other countries

Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)N2XYRY 3x16 RM 0,6/1 kVEquivalentevery value the same
South AfricaSANS 1507-4no letters for this buildCloseInner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm; Wire armour wire diameter 1.6 → 0.9 mm; Sheath material: not in the equivalent
United KingdomBS 5467Cu/XLPE/PVC/SWA/PVC 3x16 0,6/1 kV (to BS 5467)Closebuilt the British way: the armour on an extruded bedding, no separation sheath; Inner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm; Wire armour wire diameter 1.6 → 1.25 mm
IndiaIS 7098 (Part 1)2XWY 3x16 1100 VCloserated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm

No equivalent in: BS 6724 (asks another sheath compound); BS 7846 (asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

CU/XLPE/PVC/SWA/ PVC as the cable designer builds it, 3x16 0.6/1 kV

Overall diameter 24.8 mm, about 1,430 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP13.6
Inner covering / beddingPVC1.015.6
SheathPVC1.218.0
Wire armourSteel36 × 1.6021.2
SheathPVC1.824.8

CU/XLPE/PVC/SWA/ PVC on a drum

The smallest drum that passes every check, for 24.8 mm and about 1,430 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 11859–880 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG10 of 151,706–1,739 kg

Barrel at least 15 × OD = 372 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: CU/XLPE/PVC/SWA/ PVC

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 96 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.6 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

CU/XLPE/PVC/SWA/ PVC belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables

Terms on this page: steel wire armour

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with CU/XLPE/PVC/SWA/ PVC

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designations

CU/XLPE/PVC/SWA/ PVC