CU/XLPE/CWS/PE
CU/XLPE/CWS/PE is a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable designation: CU = Copper Conductor; XLPE = Cross-Linked Polyethylene (XLPE); CWS = Copper Wire Screen (concentric copper wires); PE = Polyethylene (PE).
1 coding system recognises this code
Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice)
| Symbol | Meaning |
|---|---|
CU | Copper Conductor |
XLPE | Cross-Linked Polyethylene (XLPE) |
CWS | Copper Wire Screen (concentric copper wires) |
PE | Polyethylene (PE) |
How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code
Fire behaviour (EU CPR)
PE sheath (PE).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
CU/XLPE/CWS/PE as the cable designer builds it, 3x95/25 12/20 kV
Overall diameter 63.3 mm, about 5,150 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.60 | 12.7 |
| Insulation | XLPE | 5.5 | 23.7 |
| Insulation screen (semicon) | Semiconducting | 0.80 | 25.3 |
| Filler | Semiconducting | 54.5 | |
| Inner covering / bedding | Semiconducting | 0.60 | 55.7 |
| Wire screen | Copper | 65 × 0.70 | 57.3 |
| Sheath | PE | 3.0 | 63.3 |
CU/XLPE/CWS/PE on a drum
The smallest drum that passes every check, for 63.3 mm and about 5,150 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 66 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG | 5 of 6 | 3,750–3,815 kg |
| 1,000 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
Barrel at least 20 × OD = 1,266 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: CU/XLPE/CWS/PE
CU/XLPE/CWS/PE belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables