CU/PVC/PVC
CU/PVC/PVC is a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable designation: CU = Copper Conductor; PVC = Polyvinyl Chloride (PVC); PVC = Polyvinyl Chloride (PVC).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of CU/PVC/PVC 3x16 0.6/1 kV:
CU/PVC/PVC: CU = Copper Conductor; PVC = Polyvinyl Chloride (PVC); PVC = Polyvinyl Chloride (PVC)3x16 0.6/1 kV: 3 cores, each copper 16 mm²; rated voltage 0.6/1 kV
Related cable types: CU/PVC/PVC/STA/PVC · pvc/pvc
Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice)
| Symbol | Meaning |
|---|---|
CU | Copper Conductor |
PVC | Polyvinyl Chloride (PVC) |
PVC | Polyvinyl Chloride (PVC) |
How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code
How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code
A Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designation (UK / International) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 119 symbols for this system.
What does CU mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? CU means Copper Conductor.
What does PVC mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? PVC means Polyvinyl Chloride (PVC).
Fire behaviour (EU CPR)
PVC sheath (PVC).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
CU/PVC/PVC: equivalents in other countries
Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 3-G (DIN VDE 0276-603) | NYY 3x16 RM 0,6/1 kV | Equivalent | every value the same |
| India | IS 1554 (Part 1) | YY 3x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 20.47 → 19.07 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
CU/PVC/PVC as the cable designer builds it, 3x16 0.6/1 kV
Overall diameter 20.5 mm, about 780 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Filler | PP | 14.9 | |
| Inner covering / bedding | PVC | 1.0 | 16.9 |
| Sheath | PVC | 1.8 | 20.5 |
CU/PVC/PVC on a drum
The smallest drum that passes every check, for 20.5 mm and about 780 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 10 of 10 | 461–468 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 13 of 13 | 924–945 kg |
Barrel at least 15 × OD = 307 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: CU/PVC/PVC
CU/PVC/PVC belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with CU/PVC/PVC
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designations