AYKY-J
AYKY-J is a CSN (Czech Republic, Slovakia) cable designation: A = Aluminium conductor; Y = PVC insulation, normal type; K = kabel: a cable proper, for fixed installation; Y = PVC sheath; -J = With a green-yellow protective core (written J, (J) or inside the count: 4J1,5); AYKY = AYKY: aluminium installation cable, PVC insulation and PVC sheath, 450/750 V (listed with the NKT aluminium-core cables). 450/750 V. TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab).
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of AYKY-J:
AYKY-J: A = Aluminium conductor; Y = PVC insulation, normal type; K = kabel: a cable proper, for fixed installation; Y = PVC sheath; -J = With a green-yellow protective core (written J, (J) or inside the count: 4J1,5); AYKY = AYKY: aluminium installation cable, PVC insulation and PVC sheath, 450/750 V (listed with the NKT aluminium-core cables). 450/750 V. TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab)
Related cable types: AYKY
CSN (Czech Republic, Slovakia)
| Symbol | Meaning |
|---|---|
A | Aluminium conductor |
Y | PVC insulation, normal type |
K | kabel: a cable proper, for fixed installation |
Y | PVC sheath |
-J | With a green-yellow protective core (written J, (J) or inside the count: 4J1,5) |
AYKY | AYKY: aluminium installation cable, PVC insulation and PVC sheath, 450/750 V (listed with the NKT aluminium-core cables). 450/750 V. TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab) |
What is AYKY cable?
AYKY: aluminium installation cable, PVC insulation and PVC sheath, 450/750 V (listed with the NKT aluminium-core cables). Rating: 450/750 V. Standard: TP-KK-134/01 (NKT); TP PRAKAB 01/03 (Prakab).
Size range 3x10 to 5x16 for the 450/750 V cable per the NKT programme; larger sizes are the 1-AYKY family. Counts: 4J1,5, 4Bx1,5 and 4-J all mean 4 cores including a green-yellow one; the B / C / D letters after a count are colour-scheme codes of the old CSN 33 0165 table, not a "without protective core" flag. 3x150+70 is three 150 mm2 cores plus one smaller 70 mm2 core (PE or PEN).
Documents and pages the readings were taken from
CSN (Czech Republic, Slovakia): how to read the cable type names
Fire behaviour (EU CPR)
PVC sheath (Y, AYKY).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with AYKY-J
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.