AXKJ
AXKJ is a SS 424 17 01 (Sweden) cable designation: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); K = Polyvinyl Chloride (PVC); J = Underground Use.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of AXKJ 3x95 0.6/1 kV:
AXKJ: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); K = Polyvinyl Chloride (PVC); J = Underground Use3x95 0.6/1 kV: 3 cores, each aluminium 95 mm²; rated voltage 0.6/1 kV
Related cable types: AXLJ
SS 424 17 01 (Sweden)
| Symbol | Meaning |
|---|---|
A | Aluminium Conductor |
X | Cross-Linked Polyethylene (XLPE, PEX) |
K | Polyvinyl Chloride (PVC) |
J | Underground Use |
How to read a SS 424 17 01 (Sweden) cable code
A SS 424 17 01 (Sweden) designation (Sweden) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 90 symbols for this system.
What does A mean in a SS 424 17 01 (Sweden) cable code? A means Aluminium Conductor; or Screen Of Aluminium Foil And/Or Aluminium Wire.
What does X mean in a SS 424 17 01 (Sweden) cable code? X means Cross-Linked Polyethylene (XLPE, PEX); or Polyvinyl Chloride (PVC), Oval Section; or Without Protective Conductor (Size Field).
What does K mean in a SS 424 17 01 (Sweden) cable code? K means Polyvinyl Chloride (PVC).
What does J mean in a SS 424 17 01 (Sweden) cable code? J means Steel Wire Conductor; or Steel Tape Armour; or Underground Use; or For Laying In Ground.
Fire behaviour (EU CPR)
PVC sheath (K).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
AXKJ: equivalents in other countries
Shown for 3x95 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | NA2XY 3x95 RM 0,6/1 kV | Equivalent | every value the same |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding 1.2 → 1.4 mm; Sheath 2 → 2.2 mm; Wire armour material: only in the equivalent; Overall diameter 35.92 → 40.72 mm |
| India | IS 7098 (Part 1) | A2XY 3x95 1100 V | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1.2 → 0.4 mm; Sheath 2 → 2.2 mm; this cable as built misses 1 of its rules |
No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (not in its cable tables, armoured cables only, asks another sheath compound).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
AXKJ as the cable designer builds it, 3x95 0.6/1 kV
Overall diameter 35.9 mm, about 1,510 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 1.1 | 13.7 |
| Filler | PP | 29.5 | |
| Inner covering / bedding | PVC | 1.2 | 31.9 |
| Sheath | PVC | 2.0 | 35.9 |
AXKJ on a drum
The smallest drum that passes every check, for 35.9 mm and about 1,510 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 10 | 1,031–1,064 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 9 | 1,989–2,110 kg |
Barrel at least 15 × OD = 539 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: AXKJ
AXKJ belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with AXKJ
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.