AHXCMK-WTL
AHXCMK-WTL is a SFS 5636 (Finland) cable designation: A = A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin'); H = H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4); X = Cross-linked polyethylene (PEX) insulation; C = C: copper wire screen on each core (HD 620 S3 10-F Tables A4, A8, A23); M = Plastic sheath (of each core); K = Cable; -WTL = -WTL: watertight conductor and copper wire screen, Types 10F-2, 10F-11 and 10F-12 (HD 620 S3 10-F Tables A8, A23); AHXCMK-WTL = AHXCMK-WTL: three single-core medium-voltage cables laid up, aluminium conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2). 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). HD 620 S3:2023 section 10-F, Table A8 (p. 10-F-42) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard.
1 coding system recognises this code
SFS 5636 (Finland)
| Symbol | Meaning |
|---|---|
A | A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin') |
H | H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4) |
X | Cross-linked polyethylene (PEX) insulation |
C | C: copper wire screen on each core (HD 620 S3 10-F Tables A4, A8, A23) |
M | Plastic sheath (of each core) |
K | Cable |
-WTL | -WTL: watertight conductor and copper wire screen, Types 10F-2, 10F-11 and 10F-12 (HD 620 S3 10-F Tables A8, A23) |
AHXCMK-WTL | AHXCMK-WTL: three single-core medium-voltage cables laid up, aluminium conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2). 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). HD 620 S3:2023 section 10-F, Table A8 (p. 10-F-42) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard |
What is AHXCMK-WTL cable?
AHXCMK-WTL: three single-core medium-voltage cables laid up, aluminium conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A8 (p. 10-F-42) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard.
Type 10F-2: pre-assembled single cores, conductor and screen watertight, PE sheath (Table A8). HD 620 S3 10-F prints the name in a row with its conductor, metal screen and sheath; it does not spell out the letters, so the split follows the Finnish key (fi.wikipedia, secondary) and the table columns.
Documents and pages the readings were taken from
- HD 620 S3:2023 10-F Table A8 (p. 10-F-42); scope 1, p. 10-F-3
- fi.wikipedia.org
Laying, sizes and datasheet: AHXCMK-WTL
Terms on this page: insulation screen
Work with AHXCMK-WTL
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.