How to read a cable code: guides per coding system · SFS 5636 (Finland) · Finland
SFS 5636 (Finland): how to read the cable type names
Each name in SFS 5636 (Finland) stands for a whole cable type: AHXAMK-W, for example, comes with its own construction, standard and rating. The decoder knows 21 types of this system. Below: how the names are built, every type with its rating, and the sources the table names.
How a name is built
The type table splits each name into parts and records what each part means. A few names taken apart:
AHXAMK-W
| A | A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin') |
| H | H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4) |
| X | Cross-linked polyethylene (PEX) insulation |
| A | A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20) |
| M | Plastic sheath (of each core) |
| K | Cable |
| -W | Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis') |
AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3)
AHXAMK-WS
| A | A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin') |
| H | H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4) |
| X | Cross-linked polyethylene (PEX) insulation |
| A | A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20) |
| M | Plastic sheath (of each core) |
| K | Cable |
| -WS | -WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15) |
AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4)
HXAMK-W
| H | H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4) |
| X | Cross-linked polyethylene (PEX) insulation |
| A | A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20) |
| M | Plastic sheath (of each core) |
| K | Cable |
| -W | Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis') |
HXAMK-W: three copper cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3)
AHXAMK-WM
| A | A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin') |
| H | H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4) |
| X | Cross-linked polyethylene (PEX) insulation |
| A | A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20) |
| M | Plastic sheath (of each core) |
| K | Cable |
| -WM | -WM: Type 10F-6, watertight, laid up round an insulated steel messenger (HD 620 S3 10-F Table A20) |
AHXAMK-WM: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round an insulated steel messenger, watertight (HD 620 type 10F-6)
Every part used in the names
| Part | Meaning | Used in |
|---|---|---|
| H | H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4) | AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL AHXCMK-WTC HXCMK HXCMK-WTL HXCMK-WTC AHXCMKM-WTL |
| X | Cross-linked polyethylene (PEX) insulation | AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL AHXCMK-WTC HXCMK HXCMK-WTL HXCMK-WTC AHXCMKM-WTL |
| K | Cable | AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL AHXCMK-WTC HXCMK HXCMK-WTL HXCMK-WTC AHXCMKM-WTL |
| A | A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin') | AHXAMK-W AHXAMK-WS AHXAMK-WM AHXAMK-WP AMCMK AMMK AXMK AHXCMK AHXCMK-WTL AHXCMK-WTC AHXCMKM-WTL |
| M | Plastic sheath (of each core) | AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL HXCMK HXCMK-WTL AHXCMKM-WTL |
| A | A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20) | AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP |
| K | Cable, power cable ('Kaapeli (voimakaapeli)') | MCMK AMCMK AMMK AXMK MCCMK-HF |
| C | C: copper wire screen on each core (HD 620 S3 10-F Tables A4, A8, A23) | AHXCMK AHXCMK-WTL HXCMK HXCMK-WTL AHXCMKM-WTL |
| C | Concentric copper conductor ('Konsentrinen kupari, nolla- tai suojajohdin') | MCMK AMCMK MCCMK-HF |
| -WTL | -WTL: watertight conductor and copper wire screen, Types 10F-2, 10F-11 and 10F-12 (HD 620 S3 10-F Tables A8, A23) | AHXCMK-WTL HXCMK-WTL AHXCMKM-WTL |
| -W | Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis') | AHXAMK-W HXAMK-W |
| M | M (1st): PVC insulation (HD 603 Part 3, PVC insulated cables) | AMCMK AMMK |
| M | M (2nd): PVC sheath, compound DMV 9, black (HD 603 3-F No. 6.1, 6.2) | AMCMK AMMK |
| M | M: plastic sheath ('muovivaippa'); PVC on the maker sheets | AXMK MMO |
| M | M: plastic insulation ('M = Muovi, muovieristetty'); PVC on the maker sheets | MKEM MMO |
| C | C: common copper wire screen over the laid-up cores (HD 620 S3 10-F Table A27) | AHXCMK-WTC HXCMK-WTC |
| M | M: common oversheath, PE (Type 10F-13) or PVC (Type 10F-14) (HD 620 S3 10-F Table A27) | AHXCMK-WTC HXCMK-WTC |
| -WTC | -WTC: watertight conductor, common copper wire screen, Types 10F-13 and 10F-14 (HD 620 S3 10-F Table A27) | AHXCMK-WTC HXCMK-WTC |
| -WS | -WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15) | AHXAMK-WS |
| -WM | -WM: Type 10F-6, watertight, laid up round an insulated steel messenger (HD 620 S3 10-F Table A20) | AHXAMK-WM |
| -WP | -WP: Type 10F-5, watertight, solid aluminium conductors, pre-assembled (HD 620 S3 10-F Table A17) | AHXAMK-WP |
| M | 1st letter: plastic-insulated ('muovieristetty (MCMK)'; fi.wikipedia: 'M = Muovi'); PVC per the Reka sheet | MCMK |
| M | 2nd M: plastic sheath ('muovivaippa (MCMK)'); UV-protected PVC per the Reka sheet | MCMK |
| M | 1st letter: plastic insulation ('muovieristetty'; fi.wikipedia 'M = Muovi'); PVC per the Reka sheet | MMJ |
| M | 2nd letter: plastic sheath ('muovivaippa'); UV-protected PVC per the Reka sheet | MMJ |
| J | Plastic-sheathed cable or cord ('Tarkoittaa muovivaippakaapelia/johtoa. MMJ') | MMJ |
| X | X: cross-linked polyethylene (PEX) insulation ('Silloitettu polyeteeni') | AXMK |
| K | K: stranded conductor ('kerrattu johdin (MKEM)') | MKEM |
| E | E: fine-wire conductor ('hienolankainen kaapelin johdin (MKEM)') | MKEM |
| O | O: control cable ('ohjauskaapeli (MMO)') | MMO |
| M | M: plastic insulation ('M = Muovi'); XLPE on the Prysmian sheet | MCCMK-HF |
| C | C (1st): EMC screen of metallised foil over the cores (Prysmian sheet) | MCCMK-HF |
| M | M: plastic sheath ('muovivaippa'); halogen-free polymer on the Prysmian sheet | MCCMK-HF |
| -HF | HF: halogen free | MCCMK-HF |
| M | M (last): common oversheath over the laid-up cores, PVC (Type 10F-11) or PE (Type 10F-12) (HD 620 S3 10-F Table A23) | AHXCMKM-WTL |
What the type table says about the names
Quoted from the notes of the type table, with the types they belong to.
- Finnish letters are their own system, not SS 424 17 01: H, M, K and W do other jobs here. (AHXAMK-W)
- The earth core is written after the size, not in the letters: MMJ 3x1,5 S has one green-yellow core, MMJ 3x1,5 N has none (fi.wikipedia, Kaapeleiden merkintätavat). (MMJ)
- J does not mean a green-yellow core. (MMJ)
Every type in SFS 5636 (Finland)
| Type | Description | Rating |
|---|---|---|
AHXAMK-W | AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
AHXAMK-WS | AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
HXAMK-W | HXAMK-W: three copper cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
AHXAMK-WM | AHXAMK-WM: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round an insulated steel messenger, watertight (HD 620 type 10F-6) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
AHXAMK-WP | AHXAMK-WP: three solid aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up, watertight (HD 620 type 10F-5) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
MCMK | MCMK: PVC-insulated, PVC-sheathed copper power cable with a concentric copper conductor (neutral / PE / screen), 0,6/1 kV | 0,6/1 (1,2) kV, 70 C conductor, 160 C short circuit (5 s) |
MMJ | MMJ: plastic-insulated, plastic-sheathed installation cable, copper, PVC, 300/500 V; a trailing S means one core is green-yellow earth, N means none | 300/500 V, 70 C conductor, 160 C short circuit (5 s) |
AMCMK | AMCMK: aluminium power cable, PVC insulation, concentric copper conductor, PVC sheath, 0,6/1 kV | 0,6/1 (1,2) kV, 70 C conductor, 160 C short circuit |
AMMK | AMMK: aluminium power cable, PVC insulation, PVC sheath, no concentric conductor, 0,6/1 kV (HD 603 type 3F-2) | 0,6/1 kV (HD 603 title); 1x35 to 1x1000, 3x50+25 to 3x300+150 and 4x16 to 4x300 mm² (Table 3) |
AXMK | AXMK: aluminium power cable, PEX (XLPE) insulation, PVC sheath, 0,6/1 kV, not for laying in the ground | 0,6/1 (1,2) kV, 90 C conductor, 250 C short circuit (5 s) |
MKEM | MKEM: PVC-insulated single-core wire with a flexible fine-wire copper conductor, 450/750 V (H07V-K class); MKEM-HF halogen free | 450/750 V, 70 C conductor, 160 C short circuit (MKEM-HF sheet) |
MMO | MMO: PVC-insulated, PVC-sheathed control cable with numbered cores, 450/750 V, not for laying in the ground | 450/750 V |
MHS | MHS: indoor telecommunication cable, twisted pairs of 0,5 mm solid tinned copper, PE insulation, overall aluminium-polyester screen with a drain wire; MHS LSZH with a halogen-free sheath | 100 V maximum operating voltage (Nexans) |
MCCMK-HF | MCCMK-HF: halogen-free 1 kV power cable, XLPE-insulated copper cores under an EMC screen of metallised foil, concentric copper conductor, halogen-free sheath | 0,6/1 kV, Um 1,2 kV; 90 C conductor, 250 C short circuit |
AHXCMK | AHXCMK: single-core medium-voltage cable, aluminium conductor, XLPE, copper wire screen, PVC sheath (HD 620 type 10F-1) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
AHXCMK-WTL | AHXCMK-WTL: three single-core medium-voltage cables laid up, aluminium conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
AHXCMK-WTC | AHXCMK-WTC: three-core medium-voltage cable, aluminium conductors, XLPE, common copper wire screen, PE (10F-13) or PVC (10F-14) oversheath | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
HXCMK | HXCMK: single-core medium-voltage cable, copper conductor, XLPE, copper wire screen, PVC sheath (HD 620 type 10F-1) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
HXCMK-WTL | HXCMK-WTL: three single-core medium-voltage cables laid up, copper conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
HXCMK-WTC | HXCMK-WTC: three-core medium-voltage cable, copper conductors, XLPE, common copper wire screen, PE (10F-13) or PVC (10F-14) oversheath | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
AHXCMKM-WTL | AHXCMKM-WTL: three aluminium cores, each with XLPE, a copper wire screen and its own sheath, laid up under a common oversheath, watertight (HD 620 types 10F-11, 10F-12) | 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1) |
Common questions
What is AHXAMK-W cable?
AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A12 (p. 10-F-45) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard; the makers name SFS 5636. The name reads: A (A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')) + H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -W (Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')).
What is AHXAMK-WS cable?
AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A15 (p. 10-F-47) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard. The name reads: A (A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')) + H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -WS (-WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15)).
What is the difference between AHXAMK-W and AHXAMK-WS?
AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3), 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4), 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). The names differ in: AHXAMK-W: -W (Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')); AHXAMK-WS: -WS (-WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15)).
SFS 5636 (Finland): what does M mean in a cable name?
M has more than one meaning, depending on the type: Plastic sheath (of each core) (AHXAMK-W, AHXAMK-WS, HXAMK-W, AHXAMK-WM +6); M (1st): PVC insulation (HD 603 Part 3, PVC insulated cables) (AMCMK, AMMK); M (2nd): PVC sheath, compound DMV 9, black (HD 603 3-F No. 6.1, 6.2) (AMCMK, AMMK); M: plastic sheath ('muovivaippa'); PVC on the maker sheets (AXMK, MMO); M: plastic insulation ('M = Muovi, muovieristetty'); PVC on the maker sheets (MKEM, MMO); M: common oversheath, PE (Type 10F-13) or PVC (Type 10F-14) (HD 620 S3 10-F Table A27) (AHXCMK-WTC, HXCMK-WTC); 1st letter: plastic-insulated ('muovieristetty (MCMK)'; fi.wikipedia: 'M = Muovi'); PVC per the Reka sheet (MCMK); 2nd M: plastic sheath ('muovivaippa (MCMK)'); UV-protected PVC per the Reka sheet (MCMK); 1st letter: plastic insulation ('muovieristetty'; fi.wikipedia 'M = Muovi'); PVC per the Reka sheet (MMJ); 2nd letter: plastic sheath ('muovivaippa'); UV-protected PVC per the Reka sheet (MMJ); M: plastic insulation ('M = Muovi'); XLPE on the Prysmian sheet (MCCMK-HF); M: plastic sheath ('muovivaippa'); halogen-free polymer on the Prysmian sheet (MCCMK-HF); M (last): common oversheath over the laid-up cores, PVC (Type 10F-11) or PE (Type 10F-12) (HD 620 S3 10-F Table A23) (AHXCMKM-WTL).
What is HXAMK-W cable?
HXAMK-W: three copper cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A12 (p. 10-F-45) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard. The name reads: H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -W (Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')).
What is AHXAMK-WM cable?
AHXAMK-WM: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round an insulated steel messenger, watertight (HD 620 type 10F-6). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A20 (p. 10-F-50) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard; the makers name SFS 5636. The name reads: A (A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')) + H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -WM (-WM: Type 10F-6, watertight, laid up round an insulated steel messenger (HD 620 S3 10-F Table A20)).
Sources the type table names
Standards named in the table
- HD 620 S3:2023 section 10-F, Table A12 (p. 10-F-45) (provisional type designation)
- XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard
- the makers name SFS 5636
- HD 620 S3:2023 section 10-F, Table A15 (p. 10-F-47) (provisional type designation)
- HD 620 S3:2023 section 10-F, Table A20 (p. 10-F-50) (provisional type designation)
- HD 620 S3:2023 section 10-F, Table A17 (p. 10-F-48) (provisional type designation)
- SFS 4880, SEK TS 424 14 18-1, HD 603 3 F & L (Reka datasheet)
- SFS 2091, SS 424 02 19-3, NEK 535 (Reka datasheet)
- HD 603 S1:1994/A2:2003 section 3-F, Table 3 (p. 3-F-11): AMCMK, type 3F-1 with concentric conductor (contents p. 0-3), concentric conductor of one layer of copper wires with a copper contact tape (No. 5.1, p. 3-F-4), outer sheath DMV 9 PVC (No. 6.1)
- makers: SFS 4880, HD 603-3F, IEC 60502-1 (Draka)
- SFS 4880, SEK TS 424 14 18-1, HD 603 3 F & L (Reka)
- HD 603 S1:1994/A2:2003 section 3-F, Table 3 (p. 3-F-11): AMMK, aluminium cables of type 3F-2, without concentric conductor (contents p. 0-3)
- outer sheath DMV 9 weather resistant PVC, black (No. 6.1, 6.2, p. 3-F-4). seen: standard
- SFS 4879, SEK TS 424 14 18-1, HD 603 5 D & O (Reka)
- EN 50525-3-31 (MKEM-HF, Prysmian)
- Draka MKEM 90 450/750 V
- Draka MMO 450/750 V (Taloon listing)
- SFS 5739 (Nexans sheet)
- SFS 5546 (national construction), IEC 60502-1, EN 50575 (Prysmian)
- HD 620 S3:2023 section 10-F, Table A4 (p. 10-F-39) (provisional type designation)
- HD 620 S3:2023 section 10-F, Table A8 (p. 10-F-42) (provisional type designation)
- HD 620 S3:2023 section 10-F, Table A27 (p. 10-F-54) (provisional type designation)
- HD 620 S3:2023 section 10-F, Table A23 (p. 10-F-52) (provisional type designation)
Documents and pages the readings were taken from
- HD 620 S3:2023 10-F Table A12 (p. 10-F-45); scope 1, p. 10-F-3
- fi.prysmian.com/sites/fi.prysmian.com/files/2024-03/Prysmian-Energia-te…
- fi.wikipedia.org/wiki/Kaapeleiden_merkintätavat
- esvika.ee/wp-content/uploads/2017/06/AHXAMK-W-datasheet.pdf
- HD 620 S3:2023 10-F Table A15 (p. 10-F-47); scope 1, p. 10-F-3
- HD 620 S3:2023 10-F Table A20 (p. 10-F-50); scope 1, p. 10-F-3
- HD 620 S3:2023 10-F Table A17 (p. 10-F-48); scope 1, p. 10-F-3
- reka.fi/datasheet/product/6410006031153
- reka.fi/datasheet/product/6410006031849
- cdn.erply.com/files/396198/MCMK-tooteleht.pdf
- reka.fi/datasheet/product/6410004069707
- reka.fi/datasheet/product/6410004069226
- HD 603 S1:1994/A2:2003 3-F Table 3, p. 3-F-11; No. 5.1, 6.1, p. 3-F-4
- taloon.com/media/attachments/draka/alumiinivoimakaapeli_amcmk_draka.pdf
- reka.fi/datasheet/category/C0063
- HD 603 S1:1994/A2:2003 3-F Table 3, p. 3-F-11; No. 6.1, 6.2, p. 3-F-4; contents p. 0-3
- reka.fi/datasheet/product/6410006262021
- onninen.fi/en/draka-power-network-cables-axmk-4x240-s-an-1-kv/p/ACT212
- taloon.com/asennusjohto-draka-mkem-90-1-5-si
- pood.esvika.ee/ProductSpecifications/Download
- taloon.com/ohjauskaapeli-draka-mmo-7x1-5-s
- pood.esvika.ee/ProductSpecifications/Download
- onninen.fi/en/nexans-telekabel-inomhus-mhs-lszh-5x2x0-5-dca/p/CEA979
- datasheet.prysmiangroup.com/pdf/datasheet/en/304387
- indico.ess.eu/event/1007/contributions/83/attachments/80/144/MCCMK-HF_E…
- HD 620 S3:2023 10-F Table A4 (p. 10-F-39); scope 1, p. 10-F-3
- HD 620 S3:2023 10-F Table A8 (p. 10-F-42); scope 1, p. 10-F-3
- HD 620 S3:2023 10-F Table A27 (p. 10-F-54); scope 1, p. 10-F-3
- HD 620 S3:2023 10-F Table A23 (p. 10-F-52); scope 1, p. 10-F-3
Taken from the type table of this site, with the sources named above. Check the manufacturer's datasheet before you specify a cable.