How to read a cable code: guides per coding system · SFS 5636 (Finland) · Finland

SFS 5636 (Finland): how to read the cable type names

Each name in SFS 5636 (Finland) stands for a whole cable type: AHXAMK-W, for example, comes with its own construction, standard and rating. The decoder knows 21 types of this system. Below: how the names are built, every type with its rating, and the sources the table names.

How a name is built

The type table splits each name into parts and records what each part means. A few names taken apart:

AHXAMK-W

AA (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')
HH: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)
XCross-linked polyethylene (PEX) insulation
AA (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)
MPlastic sheath (of each core)
KCable
-WLongitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')

AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3)

AHXAMK-WS

AA (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')
HH: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)
XCross-linked polyethylene (PEX) insulation
AA (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)
MPlastic sheath (of each core)
KCable
-WS-WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15)

AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4)

HXAMK-W

HH: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)
XCross-linked polyethylene (PEX) insulation
AA (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)
MPlastic sheath (of each core)
KCable
-WLongitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')

HXAMK-W: three copper cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3)

AHXAMK-WM

AA (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')
HH: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)
XCross-linked polyethylene (PEX) insulation
AA (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)
MPlastic sheath (of each core)
KCable
-WM-WM: Type 10F-6, watertight, laid up round an insulated steel messenger (HD 620 S3 10-F Table A20)

AHXAMK-WM: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round an insulated steel messenger, watertight (HD 620 type 10F-6)

Every part used in the names

PartMeaningUsed in
HH: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL AHXCMK-WTC HXCMK HXCMK-WTL HXCMK-WTC AHXCMKM-WTL
XCross-linked polyethylene (PEX) insulationAHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL AHXCMK-WTC HXCMK HXCMK-WTL HXCMK-WTC AHXCMKM-WTL
KCableAHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL AHXCMK-WTC HXCMK HXCMK-WTL HXCMK-WTC AHXCMKM-WTL
AA (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')AHXAMK-W AHXAMK-WS AHXAMK-WM AHXAMK-WP AMCMK AMMK AXMK AHXCMK AHXCMK-WTL AHXCMK-WTC AHXCMKM-WTL
MPlastic sheath (of each core)AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP AHXCMK AHXCMK-WTL HXCMK HXCMK-WTL AHXCMKM-WTL
AA (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)AHXAMK-W AHXAMK-WS HXAMK-W AHXAMK-WM AHXAMK-WP
KCable, power cable ('Kaapeli (voimakaapeli)')MCMK AMCMK AMMK AXMK MCCMK-HF
CC: copper wire screen on each core (HD 620 S3 10-F Tables A4, A8, A23)AHXCMK AHXCMK-WTL HXCMK HXCMK-WTL AHXCMKM-WTL
CConcentric copper conductor ('Konsentrinen kupari, nolla- tai suojajohdin')MCMK AMCMK MCCMK-HF
-WTL-WTL: watertight conductor and copper wire screen, Types 10F-2, 10F-11 and 10F-12 (HD 620 S3 10-F Tables A8, A23)AHXCMK-WTL HXCMK-WTL AHXCMKM-WTL
-WLongitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')AHXAMK-W HXAMK-W
MM (1st): PVC insulation (HD 603 Part 3, PVC insulated cables)AMCMK AMMK
MM (2nd): PVC sheath, compound DMV 9, black (HD 603 3-F No. 6.1, 6.2)AMCMK AMMK
MM: plastic sheath ('muovivaippa'); PVC on the maker sheetsAXMK MMO
MM: plastic insulation ('M = Muovi, muovieristetty'); PVC on the maker sheetsMKEM MMO
CC: common copper wire screen over the laid-up cores (HD 620 S3 10-F Table A27)AHXCMK-WTC HXCMK-WTC
MM: common oversheath, PE (Type 10F-13) or PVC (Type 10F-14) (HD 620 S3 10-F Table A27)AHXCMK-WTC HXCMK-WTC
-WTC-WTC: watertight conductor, common copper wire screen, Types 10F-13 and 10F-14 (HD 620 S3 10-F Table A27)AHXCMK-WTC HXCMK-WTC
-WS-WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15)AHXAMK-WS
-WM-WM: Type 10F-6, watertight, laid up round an insulated steel messenger (HD 620 S3 10-F Table A20)AHXAMK-WM
-WP-WP: Type 10F-5, watertight, solid aluminium conductors, pre-assembled (HD 620 S3 10-F Table A17)AHXAMK-WP
M1st letter: plastic-insulated ('muovieristetty (MCMK)'; fi.wikipedia: 'M = Muovi'); PVC per the Reka sheetMCMK
M2nd M: plastic sheath ('muovivaippa (MCMK)'); UV-protected PVC per the Reka sheetMCMK
M1st letter: plastic insulation ('muovieristetty'; fi.wikipedia 'M = Muovi'); PVC per the Reka sheetMMJ
M2nd letter: plastic sheath ('muovivaippa'); UV-protected PVC per the Reka sheetMMJ
JPlastic-sheathed cable or cord ('Tarkoittaa muovivaippakaapelia/johtoa. MMJ')MMJ
XX: cross-linked polyethylene (PEX) insulation ('Silloitettu polyeteeni')AXMK
KK: stranded conductor ('kerrattu johdin (MKEM)')MKEM
EE: fine-wire conductor ('hienolankainen kaapelin johdin (MKEM)')MKEM
OO: control cable ('ohjauskaapeli (MMO)')MMO
MM: plastic insulation ('M = Muovi'); XLPE on the Prysmian sheetMCCMK-HF
CC (1st): EMC screen of metallised foil over the cores (Prysmian sheet)MCCMK-HF
MM: plastic sheath ('muovivaippa'); halogen-free polymer on the Prysmian sheetMCCMK-HF
-HFHF: halogen freeMCCMK-HF
MM (last): common oversheath over the laid-up cores, PVC (Type 10F-11) or PE (Type 10F-12) (HD 620 S3 10-F Table A23)AHXCMKM-WTL

What the type table says about the names

Quoted from the notes of the type table, with the types they belong to.

  • Finnish letters are their own system, not SS 424 17 01: H, M, K and W do other jobs here. (AHXAMK-W)
  • The earth core is written after the size, not in the letters: MMJ 3x1,5 S has one green-yellow core, MMJ 3x1,5 N has none (fi.wikipedia, Kaapeleiden merkintätavat). (MMJ)
  • J does not mean a green-yellow core. (MMJ)

Every type in SFS 5636 (Finland)

TypeDescriptionRating
AHXAMK-WAHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
AHXAMK-WSAHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
HXAMK-WHXAMK-W: three copper cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
AHXAMK-WMAHXAMK-WM: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round an insulated steel messenger, watertight (HD 620 type 10F-6)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
AHXAMK-WPAHXAMK-WP: three solid aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up, watertight (HD 620 type 10F-5)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
MCMKMCMK: PVC-insulated, PVC-sheathed copper power cable with a concentric copper conductor (neutral / PE / screen), 0,6/1 kV0,6/1 (1,2) kV, 70 C conductor, 160 C short circuit (5 s)
MMJMMJ: plastic-insulated, plastic-sheathed installation cable, copper, PVC, 300/500 V; a trailing S means one core is green-yellow earth, N means none300/500 V, 70 C conductor, 160 C short circuit (5 s)
AMCMKAMCMK: aluminium power cable, PVC insulation, concentric copper conductor, PVC sheath, 0,6/1 kV0,6/1 (1,2) kV, 70 C conductor, 160 C short circuit
AMMKAMMK: aluminium power cable, PVC insulation, PVC sheath, no concentric conductor, 0,6/1 kV (HD 603 type 3F-2)0,6/1 kV (HD 603 title); 1x35 to 1x1000, 3x50+25 to 3x300+150 and 4x16 to 4x300 mm² (Table 3)
AXMKAXMK: aluminium power cable, PEX (XLPE) insulation, PVC sheath, 0,6/1 kV, not for laying in the ground0,6/1 (1,2) kV, 90 C conductor, 250 C short circuit (5 s)
MKEMMKEM: PVC-insulated single-core wire with a flexible fine-wire copper conductor, 450/750 V (H07V-K class); MKEM-HF halogen free450/750 V, 70 C conductor, 160 C short circuit (MKEM-HF sheet)
MMOMMO: PVC-insulated, PVC-sheathed control cable with numbered cores, 450/750 V, not for laying in the ground450/750 V
MHSMHS: indoor telecommunication cable, twisted pairs of 0,5 mm solid tinned copper, PE insulation, overall aluminium-polyester screen with a drain wire; MHS LSZH with a halogen-free sheath100 V maximum operating voltage (Nexans)
MCCMK-HFMCCMK-HF: halogen-free 1 kV power cable, XLPE-insulated copper cores under an EMC screen of metallised foil, concentric copper conductor, halogen-free sheath0,6/1 kV, Um 1,2 kV; 90 C conductor, 250 C short circuit
AHXCMKAHXCMK: single-core medium-voltage cable, aluminium conductor, XLPE, copper wire screen, PVC sheath (HD 620 type 10F-1)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
AHXCMK-WTLAHXCMK-WTL: three single-core medium-voltage cables laid up, aluminium conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
AHXCMK-WTCAHXCMK-WTC: three-core medium-voltage cable, aluminium conductors, XLPE, common copper wire screen, PE (10F-13) or PVC (10F-14) oversheath6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
HXCMKHXCMK: single-core medium-voltage cable, copper conductor, XLPE, copper wire screen, PVC sheath (HD 620 type 10F-1)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
HXCMK-WTLHXCMK-WTL: three single-core medium-voltage cables laid up, copper conductors, XLPE, copper wire screen, PE sheath, watertight (HD 620 type 10F-2)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
HXCMK-WTCHXCMK-WTC: three-core medium-voltage cable, copper conductors, XLPE, common copper wire screen, PE (10F-13) or PVC (10F-14) oversheath6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)
AHXCMKM-WTLAHXCMKM-WTL: three aluminium cores, each with XLPE, a copper wire screen and its own sheath, laid up under a common oversheath, watertight (HD 620 types 10F-11, 10F-12)6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1)

Common questions

What is AHXAMK-W cable?

AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A12 (p. 10-F-45) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard; the makers name SFS 5636. The name reads: A (A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')) + H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -W (Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')).

What is AHXAMK-WS cable?

AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A15 (p. 10-F-47) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard. The name reads: A (A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')) + H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -WS (-WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15)).

What is the difference between AHXAMK-W and AHXAMK-WS?

AHXAMK-W: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3), 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). AHXAMK-WS: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a steel messenger, watertight (HD 620 type 10F-4), 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). The names differ in: AHXAMK-W: -W (Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')); AHXAMK-WS: -WS (-WS: Type 10F-4, watertight, laid up round a steel messenger (HD 620 S3 10-F Table A15)).

SFS 5636 (Finland): what does M mean in a cable name?

M has more than one meaning, depending on the type: Plastic sheath (of each core) (AHXAMK-W, AHXAMK-WS, HXAMK-W, AHXAMK-WM +6); M (1st): PVC insulation (HD 603 Part 3, PVC insulated cables) (AMCMK, AMMK); M (2nd): PVC sheath, compound DMV 9, black (HD 603 3-F No. 6.1, 6.2) (AMCMK, AMMK); M: plastic sheath ('muovivaippa'); PVC on the maker sheets (AXMK, MMO); M: plastic insulation ('M = Muovi, muovieristetty'); PVC on the maker sheets (MKEM, MMO); M: common oversheath, PE (Type 10F-13) or PVC (Type 10F-14) (HD 620 S3 10-F Table A27) (AHXCMK-WTC, HXCMK-WTC); 1st letter: plastic-insulated ('muovieristetty (MCMK)'; fi.wikipedia: 'M = Muovi'); PVC per the Reka sheet (MCMK); 2nd M: plastic sheath ('muovivaippa (MCMK)'); UV-protected PVC per the Reka sheet (MCMK); 1st letter: plastic insulation ('muovieristetty'; fi.wikipedia 'M = Muovi'); PVC per the Reka sheet (MMJ); 2nd letter: plastic sheath ('muovivaippa'); UV-protected PVC per the Reka sheet (MMJ); M: plastic insulation ('M = Muovi'); XLPE on the Prysmian sheet (MCCMK-HF); M: plastic sheath ('muovivaippa'); halogen-free polymer on the Prysmian sheet (MCCMK-HF); M (last): common oversheath over the laid-up cores, PVC (Type 10F-11) or PE (Type 10F-12) (HD 620 S3 10-F Table A23) (AHXCMKM-WTL).

What is HXAMK-W cable?

HXAMK-W: three copper cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round a bare copper earth conductor, watertight (HD 620 type 10F-3). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A12 (p. 10-F-45) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard. The name reads: H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -W (Longitudinally and transversely water tight cable ('W = kaapeli on pituus- ja poikittaissuuntaan vesitiivis')).

What is AHXAMK-WM cable?

AHXAMK-WM: three aluminium cores (XLPE, aluminium laminated foil screen, PE sheath) laid up round an insulated steel messenger, watertight (HD 620 type 10F-6). Rating: 6/10 (12), 12/20 (24) and 18/30 (36) kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-F 1). Standard: HD 620 S3:2023 section 10-F, Table A20 (p. 10-F-50) (provisional type designation); XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard; the makers name SFS 5636. The name reads: A (A (1st letter): aluminium conductor ('1. kirjaimena = alumiinijohdin')) + H (H: semiconducting conductor and insulation screens, required on every cable of HD 620 S3 10-F (No. 2, 4)) + X (Cross-linked polyethylene (PEX) insulation) + A (A (2nd): aluminium laminated foil screen on each core, watertight (HD 620 S3 10-F Tables A12 to A20)) + M (Plastic sheath (of each core)) + K (Cable) + -WM (-WM: Type 10F-6, watertight, laid up round an insulated steel messenger (HD 620 S3 10-F Table A20)).

Sources the type table names

Standards named in the table

  • HD 620 S3:2023 section 10-F, Table A12 (p. 10-F-45) (provisional type designation)
  • XLPE DIX 14, sheath PVC DMV 10 or PE DMP 15 (1, p. 10-F-3). seen: standard
  • the makers name SFS 5636
  • HD 620 S3:2023 section 10-F, Table A15 (p. 10-F-47) (provisional type designation)
  • HD 620 S3:2023 section 10-F, Table A20 (p. 10-F-50) (provisional type designation)
  • HD 620 S3:2023 section 10-F, Table A17 (p. 10-F-48) (provisional type designation)
  • SFS 4880, SEK TS 424 14 18-1, HD 603 3 F & L (Reka datasheet)
  • SFS 2091, SS 424 02 19-3, NEK 535 (Reka datasheet)
  • HD 603 S1:1994/A2:2003 section 3-F, Table 3 (p. 3-F-11): AMCMK, type 3F-1 with concentric conductor (contents p. 0-3), concentric conductor of one layer of copper wires with a copper contact tape (No. 5.1, p. 3-F-4), outer sheath DMV 9 PVC (No. 6.1)
  • makers: SFS 4880, HD 603-3F, IEC 60502-1 (Draka)
  • SFS 4880, SEK TS 424 14 18-1, HD 603 3 F & L (Reka)
  • HD 603 S1:1994/A2:2003 section 3-F, Table 3 (p. 3-F-11): AMMK, aluminium cables of type 3F-2, without concentric conductor (contents p. 0-3)
  • outer sheath DMV 9 weather resistant PVC, black (No. 6.1, 6.2, p. 3-F-4). seen: standard
  • SFS 4879, SEK TS 424 14 18-1, HD 603 5 D & O (Reka)
  • EN 50525-3-31 (MKEM-HF, Prysmian)
  • Draka MKEM 90 450/750 V
  • Draka MMO 450/750 V (Taloon listing)
  • SFS 5739 (Nexans sheet)
  • SFS 5546 (national construction), IEC 60502-1, EN 50575 (Prysmian)
  • HD 620 S3:2023 section 10-F, Table A4 (p. 10-F-39) (provisional type designation)
  • HD 620 S3:2023 section 10-F, Table A8 (p. 10-F-42) (provisional type designation)
  • HD 620 S3:2023 section 10-F, Table A27 (p. 10-F-54) (provisional type designation)
  • HD 620 S3:2023 section 10-F, Table A23 (p. 10-F-52) (provisional type designation)