2XWWH
2XWWH is a BIS type names (India) cable designation: 2X = XLPE insulation (IS 17505 (Part 1) cl. 19.4); WW = Double galvanised round steel wire armour (IS 17505 (Part 1) cl. 15.1.3, 19.4); H = Zero halogen outer sheath HFS-TP 90 or HFS-XL 90 (IS 17505 (Part 1) cl. 9, 19.4); 2XWWH = 2XWWH: fire survival cable (IS 17505 (Part 1)): copper conductors under glass mica tape, XLPE insulation, extruded inner sheath, double galvanised round steel wire armour, zero halogen (HFS) outer sheath. Up to and including 1100 V a.c. and 1500 V d.c.; 90 C normal, 250 C short circuit (cl. 1); fire survival category F3, F30, F60 or F120 (cl. 3.5, Annex E), printed as "FS Cable" with the category (cl. 19.2) and in the code (cl. 19.4). IS 17505 (Part 1):2021, cable code cl. 19.4.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of 2XWWH 4x16 0.6/1 kV:
2XWWH: 2X = XLPE insulation (IS 17505 (Part 1) cl. 19.4); WW = Double galvanised round steel wire armour (IS 17505 (Part 1) cl. 15.1.3, 19.4); H = Zero halogen outer sheath HFS-TP 90 or HFS-XL 90 (IS 17505 (Part 1) cl. 9, 19.4); 2XWWH = 2XWWH: fire survival cable (IS 17505 (Part 1)): copper conductors under glass mica tape, XLPE insulation, extruded inner sheath, double galvanised round steel wire armour, zero halogen (HFS) outer sheath. Up to and including 1100 V a.c. and 1500 V d.c.; 90 C normal, 250 C short circuit (cl. 1); fire survival category F3, F30, F60 or F120 (cl. 3.5, Annex E), printed as "FS Cable" with the category (cl. 19.2) and in the code (cl. 19.4). IS 17505 (Part 1):2021, cable code cl. 19.44x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV
BIS type names (India)
| Symbol | Meaning |
|---|---|
2X | XLPE insulation (IS 17505 (Part 1) cl. 19.4) |
WW | Double galvanised round steel wire armour (IS 17505 (Part 1) cl. 15.1.3, 19.4) |
H | Zero halogen outer sheath HFS-TP 90 or HFS-XL 90 (IS 17505 (Part 1) cl. 9, 19.4) |
2XWWH | 2XWWH: fire survival cable (IS 17505 (Part 1)): copper conductors under glass mica tape, XLPE insulation, extruded inner sheath, double galvanised round steel wire armour, zero halogen (HFS) outer sheath. Up to and including 1100 V a.c. and 1500 V d.c.; 90 C normal, 250 C short circuit (cl. 1); fire survival category F3, F30, F60 or F120 (cl. 3.5, Annex E), printed as "FS Cable" with the category (cl. 19.2) and in the code (cl. 19.4). IS 17505 (Part 1):2021, cable code cl. 19.4 |
What is 2XWWH cable?
2XWWH: fire survival cable (IS 17505 (Part 1)): copper conductors under glass mica tape, XLPE insulation, extruded inner sheath, double galvanised round steel wire armour, zero halogen (HFS) outer sheath. Rating: Up to and including 1100 V a.c. and 1500 V d.c.; 90 C normal, 250 C short circuit (cl. 1); fire survival category F3, F30, F60 or F120 (cl. 3.5, Annex E), printed as "FS Cable" with the category (cl. 19.2) and in the code (cl. 19.4). Standard: IS 17505 (Part 1):2021, cable code cl. 19.4.
IS 17505 (Part 1):2021, read 2026-11-01 (standard): armoured fire survival cables with low emission of smoke and corrosive gases, fixed installation (cl. 1). Annealed plain or tinned copper to IS 8130 (cl. 4), solid or stranded 1.5 to 6 mm2, stranded from 10 mm2 (cl. 10.1), under glass mica tape (cl. 10.2); XLPE or XL-HFFR insulation by extrusion (cl. 6, 11.1); fillers and an extruded inner sheath (cl. 7, 14.1); galvanised round steel wire armour over the insulation of single-core cables and over the inner sheath of the others, at least 90 % coverage, left hand lay (cl. 15.1); outer sheath HFS-TP 90 or HFS-XL 90 (cl. 9). Cable code (cl. 19.4): insulation 2X (XLPE) or Z (XL-HFFR), armour W, WW or Wa, outer sheath H, then the fire rating F3, F30, F60 or F120; the name is built from those letters in that order (no maker name was looked for). Core colours (cl. 12.1(b)): 2 cores red, black; 3 red, yellow, blue; 4 red, yellow, blue, black; 5 red, yellow, blue, black, grey; 6 and more two adjacent cores in each layer blue and yellow, the rest grey (not drawn); or coloured strips (red, yellow, blue phases, black reduced neutral) or numerals. Fire survival categories (cl. 3.5): F 950 C for 3 h, W 650 C for 15 min then water, S 950 C for 15 min with mechanical shock; F3 all three assessed apart; F30, F60, F120 fire with impact and water jet together for 30, 60, 120 min (Annex E). Current ratings per IS 3961 (Part 6) (foreword). The glass mica tape is drawn as a tape over the conductor.
Documents and pages the readings were taken from
- IS 17505 (Part 1):2021, from https://www.standardsbis.in/: cl. 1 (p. 1), 3.5 (pp. 2 to 3), 4 to 9 (p. 3), 10 to 12 (pp. 3 to 4), 14, 15 (p. 4), 19.2, 19.4 (p. 6)
Fire behaviour (EU CPR)
Halogen-free compound (H, 2XWWH). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
2XWWH: equivalents in other countries
Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | N2XHRH 4x16 RM 0,6/1 kV | Close | this cable as built misses 1 of its rules |
| United Kingdom | BS 6724 | Cu/XLPE/LSZH/SWA/LSZH 4x16 0,6/1 kV (to BS 6724) | Close | built the British way: the armour on an extruded bedding, no separation sheath; Inner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm; Wire armour wire diameter 1.6 → 1.25 mm |
| United Kingdom | BS 7846 | Cu/XLPE/LSZH/SWA/LSZH 4x16 0,6/1 kV (to BS 7846) | Close | built the British way: the armour on an extruded bedding, no separation sheath; Inner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm; Wire armour wire diameter 1.6 → 1.25 mm |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding material LSZH → PVC; Inner covering / bedding 1 → 1.2 mm; Sheath material LSZH → PVC; Sheath 1.2 → 1.7 mm |
| India | IS 7098 (Part 1) | 2XWZ 4x16 1100 V (the code letters of IS 7098 (Part 1):2025 cl. 18.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm |
No equivalent in: BS 5467 (asks another sheath compound).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
2XWWH as the cable designer builds it, 4x16 0.6/1 kV
Overall diameter 26.4 mm, about 1,700 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 15.2 | |
| Inner covering / bedding | Halogen-free (LSZH) | 1.0 | 17.2 |
| Sheath | Halogen-free (LSZH) | 1.2 | 19.6 |
| Wire armour | Steel | 40 × 1.60 | 22.8 |
| Sheath | Halogen-free (LSZH) | 1.8 | 26.4 |
2XWWH on a drum
The smallest drum that passes every check, for 26.4 mm and about 1,700 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 10 | 994–1,015 kg |
| 1,000 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 11 of 14 | 1,976–2,009 kg |
Barrel at least 15 × OD = 396 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: 2XWWH
2XWWH belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables
Terms on this page: oversheath (outer sheath) · steel wire armour